4. Manual operation
Manual operation can be selected by entering OPERATION/3 in SETUP 1, but in order to operate the
compressor by hand you have to enter into the MANUAL menu. Push the <
ee
> key in order to go back to
the initial picture and activate <F3>.
Note:
If you are running master operation and want to change into manual operation this can be done without
having to select "MANUAL" operation under SETUP 1. From the initial picture the <F3> key is
activated, and at the moment the "START" (F4) key is pushed you change into manual operation.
01-01-94 17:25:35
MANUAL/
F6 CLA :Vi-Compressor 0.0
F5 CALIBRATE:C-pos 0.0 %
F4 START :1=Compr. 2=Pump
F3 NEW (F3) :Setpoint Vi 9.9
F2 NEW (F2) :Setpoint C-pos 999.0 %
F1 STOP : STOP
If the compressor or the pump are to be started, push "START" <F4> followed by 1 or 2. If the compressor is
started the oil pump will also be running dependent on which type of pump has been chosen, see setpoint R.
The desired capacity, at which the compressor is to run, can be stated by F2. After this the solenoid valve will
receive pulses and the capacity slide will be adjusted to the desired capacity. If -10 or 110 is entered here, the
solenoid valve will receive constant signal to lower/ increase the capacity. If the value 999 is given, capacity
regulation will be a master operation, but ignoring P
SUG START
/P
SUG STOP
and T
BRINE START
/T
BRINE
STOP
.
With the F3 key the volume ratio can be selected at which you want the compressor to run. Here, the volume
slide is also regulated by impulses. By entering 2.0 or 6.0 the signal to lower/ increase the volume ratio will be
constant. If the value 9.9 is entered the computer will compute and place the slide stop at the optimum volume
ratio given at the suction pressure and the discharge pressure. In the MANUAL picture the desired values and
the actual values for capacity and volume ratio will appear in the text field.
F1 is used for stop of compressor and pump, and "MAN.STOP" will appear on the message line.