CALIBRATION
With the F5 key a menu, which is used when calibrating the potentiometers scanning the positions of capacity
slide and slide stop, can be selected from the MANUAL picture.
01-01-93
17:25:35
MANUEL/CALIBRATE/
F6 CLA :Volume position 0
F5 :Capacity pos 0
F4 START :1=Compr. 2=Pump
F3 NEW (F3) :Setpoint Vi 2.2
F2 NEW (F2) :Setpoint C-pos 0,0 %
F1 STOP :
Stop
Starting the compressor or oil pump makes calibrating. Enter -10 in setpoint C-pos. and 6.0 in setpoint Vi. The
capacity slide will now be forced into minimum and the slide stop into maximum position. When the values of
the two upper text lines are not changed any more, the limits have been reached. The values are read and noted.
Enter now 110 for C-pos and 2.0 for Vi. The capacity slide will then run into maximum and the slide stop into
minimum. As above, the variable values of the two upper lines are read and noted when the limits have been
reached.
The 4 noted values for the maximum and minimum positions of the slides are entered under setpoint S (see
section about setpoints), after which the potentiometers are calibrated.