SET POINTS
An example of the compressor set points is shown below:
SETP A/F5
P-SUCT SETP 1
-40°C
SETP B/F5
P-SUCT START (+)
4,0°C
SETP A/F4
P-SUCT RELIEVE -45°C
SETP B/F4
P-SUCT STOP (-)
3,0°C
SETP A/F3
P-SUCT CUTOUT -47°C
SETP B/F3
PROP.ZONE (+/-)
2,0°C
SETP B/F2
DEAD ZONE (+/-)
0,5°C
SETP
SOLLW
SETP
SETP
SETP
SETP
SETP
SETP
Note:
When the compressor is running according to its own set point the compressor will never adjust the
pressure down to "P-SUCT. RELIEVE" or "P-SUCT. CUTOUT" because of "P-SUCT. STOP". It will
only be possible to achieve these two pressures if the compressor is running at manual control, or at
remote control according to external set point. As "P-SUCT. CUTOUT" is resetting itself when the
pressure has again exceeded set point for "P-SUCT. CUTOUT" the compressor will start at "remote
control operation according to external set point". At manual operation the key for start of compressor
has to be pushed again.