CELLmatic 1502 – GSV/GSF
Issue: 2.1
User Manual
08.02.2004
Page 32 of 51
Thy
-
tronic
I/S – Bjørnevej 8c – DK 7700 Thisted – Tel.: +45 97982344 – Email.: Info@thytronic.dk
DISPLAY PICTURES
Initial picture
01-01-94 17:25:35
F6 CLA :P-suct (C) 0.0 C
F5 SETUP 1 :Output (%) 0.0 %
F4 SETPOINT :Ampere (%) 0.0 %
F3 MANUAL :T-Oil (C) 0.0 C
F2 DISPLAY 2:P-discharge (B) 0.00 Bar
F1 STOP : STOP
P-SUCTION (C)
The suction pressure measured is shown here converted into degree Celsius.
OUTPUT (%)
The output is a calculated value indicating the output of the compressor in per cent.
AMPERE (%)
Showing the load of the compressor motor. Is indicated in per cent of the rated current of the motor.
T-OIL (C)
Indicating the oil temperature registered by the PT-100 sensor in the oil manifold.
P-DISCHARGE (C)
Indicating the discharge pressure in bar (normally measured in the oil separator).
All current values in this display picture are "frozen" in case of a cutout or a stop.
Display picture 2
01-01-94 17:25:35
F6 CLA :P-suct C 0.0 C
F5 SETUP 1 :P-suct setpt. C 0.0 C
F4 SETPOINT :P-discharge B 0.00 Bar
F3 MANUAL :P-oil B 0.00 Bar
F2 DISPLAY 3:C-abs % 0.0 %
F1 STOP : STOP
P-SUCTION C
The suction pressure measured is shown here converted into degree Celsius.
P-SUCTION SET POINT C
Here the set point for suction pressure is shown after which the compressor is adjusting provided it is
adjusting according to its own set point.
P-DISCHARGE B
Discharge pressure in bar measured with the pressure transmitter at the oil separator.
P-OIL PRESSURE B
Oil pressure in bar measured by the pressure transmitter in the oil manifold.
C-ABS %
If the slide stop is in minimum (Vi = 2.2) the slide valve has its longest possible travel. C-ABS is then a
linear output of this travel (0-100%). If the slide stop has been adjusted to a higher Vi the value of the
C-ABS will never reach 100%.
All values in display picture 2 are updated during standstill.