CELLmatic 1502 – GSV/GSF
Issue: 2.1
User Manual
08.02.2004
Page 34 of 51
Thy
-
tronic
I/S – Bjørnevej 8c – DK 7700 Thisted – Tel.: +45 97982344 – Email.: Info@thytronic.dk
DISPLAY PICTURES
Display picture 5
01-01-94 17:25:35
F6 CLA :Vi-compr. ( ) 0.0
F5 SETUP 1 :Vi-optimum ( ) 0.0
F4 SETPOINT :T-suct (C) 0.0 C
F3 MANUAL :T-oil sep. C 0.0 C
F2 DISPLAY 6:Operat.hour X 10 0 h
F1 STOP : STOP
Vi COMPR. ( )
Here the volume ratio is shown corresponding to the actual position of the slide stop. Steeples the
compressor can place the slide stop in positions corresponding to an internal volume ratio in the
compressor from 2.2 to 5.0.
Vi-OPTIMUM ( )
Here the volume ratio is shown which can be calculated on the bases of the discharge pressure and the
suction pressure. At the same time it is the optimum position of the slide stop.
T-SUCTION (C)
Is showing the suction temperature, measured by the PT-100 sensor placed in the suction valve.
T-OIL SEPARATOR C
The temperature measured of the oil in the oil separator.
OPERATING HOURS X 10
Here the number of operating hours is read resolved into 10 hours.
Display picture 6
01-01-94 17:25:35
F6 CLA :Injection OFF
F5 SETUP 1 :Oil pump OFF
F4 SETPOINT :Heater OFF
F3 MANUAL :Economizer OFF
F2 DISPLAY 1:EPROM XXXX
F1 STOP : STOP
INJECTION
If the injection cooling is activated that is at oil temperatures above set point for "liquid injection ON"
(set point D/F2) "ON" will appear to the right on the text line in the display.
OIL PUMP
If the oil pump is running "ON" will appear to the right on the text line.
HEATER
If the heater is switched on "ON" will appear to the right on the text line.
ECONOMIZER
If the solenoid valve in the economizer line is open "ON" will appear to the right in the display picture.
This means that the economizer is working.
EPROM XXXX
Here the programme version of the computer is indicated.