CELLmatic 1502 – GSV/GSF
Issue: 2.1
User Manual
08.02.2004
Page 36 of 51
Thy
-
tronic
I/S – Bjørnevej 8c – DK 7700 Thisted – Tel.: +45 97982344 – Email.: Info@thytronic.dk
I/O PICTURES
PT-100 Sensors, Setp 1/2
PT 100 sensors give signals on resistance inputs designated "R IN 0" to "R IN 3". These designations can be
found at the terminals in the electrical panel. The I/O picture for these inputs appears as follows:
01-01-94 17:25:35
SETUP 1/I/O/PT-100/
F6 R IN 4 :Change setp. 1/2 OFF
F5 R IN 3 :T-oil compr 0.0 C
F4 R IN 2 :T-suction 0.0 C
F3 R IN 1 :T-oil sep. C 0.0 C
F2 R IN 0 :T-discharge 0.0 C
F1 STOP : STOP
R IN 4 CHANGE SETPOINT 1/2
If under the operating forms MASTER or REMOTE WITH OWN SETPOINT it is necessary to
regulate the compressor in accordance with setpoint 2 for suction pressure (entered under setp. T) a
signal is applied at this input. When the input is OFF, regulation is in accordance with setpoint 1 for
suction pressure (entered under setp. A) or in accordance with the brine temperature (entered under
setp. E).
R IN 3 T-OIL COMPRESSOR
Oil temperature in degree Celsius measured by PT-100 sensor in oil manifold.
R IN 2 T-SUCTION
The suction gas temperature in degree Celsius measured with PT-sensor in suction valve.
R IN 1 OIL SEPERATOR
Oil temperature measured by PT-100 sensor at the bottom of oil separator.
R IN 0 T-DISCHARGE PIPE
Discharge pipe temperature in degree Celsius normally measured by PT-100 sensor in discharge pipe
between compressor and oil separator.