I/O PICTURES
DIGITAL OUTPUTS 0-11, 220V AC
03-06-96 13:48:15
SETUP. 1/I/O/J1-J7-J8/OUT 0-11/
F6 OUT 4-11 :Digital output 4-11, 220V AC
F5 OUT 3 :Volume down OFF
F4 OUT 2 :Volume up OFF
F3 OUT 1 :Capacity down OFF
F2 OUT 0 :Capacity up OFF
F1 STOP :
OUT 4-11 DIGITAL OUTPUTS 4-11, 220V AC
Function key F6 can be used to leaf to the I/O picture showing digital inputs "OUT 4" to "OUT
11"
OUT 3 VOLUME DOWN
Here the signal to the solenoid valve to reduce the volume ratio on the compressor is applied.
OUT 2
VOLUME UP
Here the signal to the solenoid valve to increase the volume ratio on the compressor is applied.
OUT 1
CAPACITY DOWN
Here the signal to the solenoid valve to reduce compressor capacity is applied.
OUT 0
CAPACITY UP
Here the signal to the solenoid valve to increase compressor capacity is applied.
01-01-94 17:25:35
SETUP 1/I/O/J1-J7-J8/OUT 0-11/OUT 4-11/
F6 OUT 8-11 :Digital outputs 4-11, 220V AC
F5 OUT 7 :Available
F4 OUT 6 :Available
F3 OUT 5 :BYPASS OFF
F2 OUT 4 :Economizer OFF
F1 STOP : STOP
OUT 8-11 DIGITAL OUTPUTS 8-11, 220V AC
Function key F6 can be used to leaf to the I/O picture showing digital inputs "OUT 8" to "OUT
11"
OUT 7
LOW LIQUID INJ
If the volume ratio is less than 4.5 and OUT 6 is ON, "low liquid injection" is selected and the
output goes "ON". The signal is significant only when "dual liquid injection" is concerned, see
description of liquid injection elsewhere in the manual.
OUT 6
HIGH LIQUID INJ
This output controls the solenoid valve for liquid injection. When the oil temperature in the oil
manifold exceeds the temperature entered under setpoint D/F2, and the output goes ON and the
solenoid valve in the liquid injection line opens. This leads refrigerant into the compressor which
then becomes cooled.
OUT 5 BYPASS
When the output goes "ON", the solenoid valve in the start bypass line opens. The output is "ON"
when pressure in the oil separator exceeds the start pressure given under setpoint U/F4 and a start
attempt is made.
OUT 4
ECONOMIZER
When the output goes "ON", the economizer is in operation. The output goes "ON" when
compressor capacity exceeds 90% and goes "OFF" when the capacity fall under 80% again.