I/O PICTURES
01-01-94 17:25:35
/J1-J7-J8/OUT 12-23/OUT 16-23/OUT 20-23
F6
F5 OUT 23 :Ready to run OFF
F4 OUT 22 :Slave > minumum OFF
F3 OUT 21 :Slave cap. down OFF
F2 OUT 20 :Slave cap. Up OFF
F1 STOP : STOP
OUT 23 READY TO RUN
This is a "Ready to run" signal to denote that all conditions are in order and the compressor is ready
to start. The output goes ON at the same time as the green lamp on the front of the panel lights up.
OUT 22 SLAVE MINIMUM
With master-slave operation, the master compressor needs to "know" whether the slave has reached
more than its minimum capacity. The condition is signalled via this output (on the slave) which goes
ON when compressor capacity is more than the sum of [setp. C/F5 + setp. T/F5].
OUT 21 SLAVE CAPACITY DOWN
If this output is "ON" the next slave will be adjusted downwards.
OUT 20 SLAVE CAPACITY UP
If this output is "ON" the next slave will be adjusted upwards.