CELLmatic 1502 – GSV/GSF
Issue: 2.1
User Manual
08.02.2004
Page 45 of 51
Thy
-
tronic
I/S – Bjørnevej 8c – DK 7700 Thisted – Tel.: +45 97982344 – Email.: Info@thytronic.dk
SURVEY OF SET POINTS
SETPOINT
MENU /
FUNCTION KEY
LOW
LIMITIN
G
VALUE
HIGH
LIMITIN
G
VALUE
PRESET
VALUE
RESTART DELAY
SETP A/ F2
0 minutes
60 minutes
30 minutes
P-SUCTION CUTOUT
SETP A/ F3
-60 °C
60 °C
-45 °C
P-SUCTION RELIEVE
SETP A/ F4
-60 °C
60 °C
-40 °C
P-SUCTION SETP 1
SETP A/ F5
-60 °C
60 °C
-30 °C
DEAD BAND ZONE
SETP B/ F2
0 °C
10 °C
0,5 °C
PROPORTIONAL
ZONE
SETP B/ F3
0 °C
10 °C
1,0 °C
P-SUCTION STOP (-)
SETP B/ F4
0 °C
10 °C
2,0 °C
P-SUCTION START
(+)
SETP B/ F5
0 °C
10 °C
2,0 °C
P-DISCH. CUTOUT
SETP C/ F2
0 °C
55 °C
45 °C
P-CISCH.. ALARM
SETP C/ F3
0 °C
55 °C
40 °C
AMP. NORMAL
SETP C/ F4
0 %
100 %
100%
MINIMUM CAPACITY
SETP C/ F5
0 %
100 %
50 %
LIQUID INJECTION
ON
SETP D/ F2
0 °C
100 °C
45 °C
LIQUID INJECT. OFF
SETP D/ F3
0 °C
100 °C
40 °C
CAP. DOWN FACTOR
SETP D/ F4
0
100
50
CAP. UP FACTOR
SETP D/ F5
0
100
25
BRINE REGULATION
SETP E/F2
0=NO
1=YES
0=NO
T-BRINE STOP-
SETP E/F3
0 °C
10 °C
5 °C
T BRINE START+
SETP E/F4
0 °C
10 °C
5 °C
T BRINE SETP.
SETP E/F5
-50°C
+50°C
0 °C
HEAT SYSTEM
ACTIV
SETP I/ F2
0=NO
1=YES
0=NO
SWITCH ON HEATER
SETP I/ F3
0 °C
100 °C
40 °C
AMPERE MAXIMUM
SETP I/ F4
0 %
150 %
110 %
TRANSFORMER
FACT
SETP I/ F5
0
5
0
MAX T-OIL CUT OUT
SETP J/ F2
0 °C
100 °C
75 °C
MAX T-OIL ALARM
SETP J/ F3
0 °C
100 °C
70 °C
MIN T-OIL CUT OUT
SETP J/ F4
0 °C
100 °C
5 °C
MIN T-OIL ALARM
SETP J/ F5
0 °C
100 °C
10 °C