SURVEY OF MESSAGE TEXTS
The below picture is an example of placing of message texts on the report and status line.
01-01-94 17:25:35
F6 :
F5 :
F4 :
F3 :
F2 :
F1 : C- MASTER MAN.STOP
This section is a survey of possible message texts appearing on the report and status line (on the bottom line in
the display). Each message text has a brief description and eventually a reference to other sections.
Gives which compressor type has been selected (SETUP 2/MENU 2).
STOP
The unit has stopped and <CLA> has
not
to be pushed until it can be started. The cause of stop is
either that the suction pressure/brine temperature is under the stop limit or that the necessary start
signal to the compressor has not been given, unless a cutout message is shown in the upper left corner.
MAN. STOP
The unit has stopped according to a message from the keyboard (<F1> has been pushed) and <CLA>
has to be pushed before the compressor can be started again.
ST.P-SUCTION
The compressor has stopped because the suction pressure is below the set point for "P-SUCTION
CUTOUT" (set point A/F3).
RELIEVE
The compressor is adjusting capacity downward (unloading) because the suction pressure is below set
point for "P-SUCTION RELIEVE" (set point A/F4).
AMPERE
The compressor is adjusting capacity downwards because the power consumption is exceeding the set
point for "AMPERE CONSUMP.NORMAL" (set point C/F4).
LIMIT
This message will only appear if the compressor is provided with liquid injection. If the volume ratio
is <3.0 and the capacity (C-POS) is exceeding 90% the compressor will adjust down to 90% if the oil
temperature exceeds (T-OIL MAX ALARM -5). At the same time the message "LIMIT" will appear
in the display.
BYPASS
The compressor is not able to start because the pressure in the oil separator is exceeding the set point
for "START PRESSURE" (set point U/F4).