SURVEY OF ALARM AND CUTOUT TEXTS
CUTOUT POIL-PSUC
If the difference between oil pressure and suction pressure falls to less than 1 bar, the compressor
stops after 20 seconds and the message CUTOUT POLIE-PS appears on the alarm line.
ALARM P-DISCH.
Discharge pressure too high (above set point C/F3).
ALARM T-DISCH.
High discharge pipe temperature (above set point L/F5).
ALARM HT-OIL
High oil temperature measured in oil manifold (above set point J/F3).
This alarm has a delay of 3 minutes.
ALARM LT-OIL
Low oil temperature in oil separator (below set point J/F5).
ALARM T-SUCTION
Temperature of suction gas (measured by PT-100 sensor placed in suction valve) too low (below set
point L/F3).
ALARM OIL DIFF.
Low oil differential pressure (below set point K/F3).
This alarm has a delay of 2 minutes.
ALARM FILTERDIF.
High pressure drop across oil filter (above set point K/F5).
This alarm has a delay of 30 seconds.