STARTING UP
If a cold start is attempted, i.e. the voltage supply has been connected to the panel after the microprocessor
battery back up has been disconnected the following picture (the cold start picture) will appear.
01-01-94 17:25:35
F6 :Screw compr. Control CELLmatic
F5 COMP.TYPE: 1=GSV 2=GSF 0
F4 COMP.SIZE:State size 0
F3 REFRIGER.:State type 0
F2 NODE NO. :State own number 0
F1 CONTINUE :The above has to be completed
In this picture, the following questions must be answered:
1=GSV
2=GSF
If the compressor is with variable volumen control – select 1.
If the compressor is with fixed volume control – select 2.
Compressor size:
Possibilities are: 50, 65, 84, 111, 147, 185, 263, 331, 412 and 562.
Ex.: 64 means that the compressor has a swept volume of 640 m
3
/hour.
Refrigerant: Possibilities are: 12=R12, 22=R22, 134=R134a, 404=R404a, 502=R502 and 717=R717.
Node number: Here, give the identification number the panel can be allocated if communication is by network.
When these questions have been answered with values the computer can accept and <F1> must be keyed to
continue. If a value has been given that subsequently must be altered without cold start, the operation can be
performed under setup or setpoints.
When <F1> is keyed, the picture shown is the "initial picture". This picture is also shown when control voltage
is connected to the panel while there is battery back up on the microprocessor, i.e. a "hot start".
01-01-94 17:25:35
F6 CLA :P-Suction (C) 0.0 C
F5 SETUP. :Output (%) 0.0 %
F4 SET POINT:Ampere (%) 0.0 %
F3 MANUAL :T-oil compr (C) 0.0 C
F2 DISPLAY 2:P-discharge (B) 0.00 Bar
F1 STOP : STOP
01-01-94 17:25:35
SETPOINT/SETP I-L/SETP. I/
F6 CLA :
F5 NEW (F5) :Transform. factor 0 %
F4 NEW (F4) :Ampere max. 110.0 %
F3 NEW (F3) :Switch on heater 40.0 C
F2 HEAT SYST:Activ 0=NO 1=YES NO
F1 STOP : STOP