line mode to battery mode, CPU pin 15 is set to LOW and turn off Q03. This causes RY01 to
be OFF and return to its normal state.
R16,D02,C10 and Q04 are used to speed up the relay action, so the power loss time can
be reduced to minimum. When UPS transfers to battery mode, C10 is charged by the +12
Volts. After the main relay makes contact, C10provides instantaneous power to the relay coils.
This increase the magnetic force and speeds up the relay to reduce the transfer time from
battery mode to line mode. See Figure W-9 for voltage changes on C10,during line to battery
mode transfers.
CPU pin 12 is used to the drive signal for RY02 (booster relay). When the input line
source voltage falls below boost active threshold, pin 12 sends a high signal to turn on Q05
(2SC1815). This actives the RY02 ,and UPS goes into the Boost mode. When the input line
voltage goes above the boost disactive threshold, the UPS returns to nominal mode by sends
a LOW signal from pin 12. This forces RY02 to switch into its normal position( OFF). At
battery mode, pin 12 is always set to LOW and RY02 is disable.
The same case as buck control, CPU pin 14 is used to the drive signal for RY03 (buck
relay). When the input line source voltage rise above buck active threshold, pin 14 sends
a high signal to turn on RY03. When the input line voltage goes below the buck disactive
threshold, The UPS returns to nominal mode by output a LOW signal from pin 14.
20
Summary of Contents for 400VA
Page 8: ...Figure S 1 Control Power circuit 6 ...
Page 9: ...CH1 C15 GND Figure W 1 Cold Start 7 ...
Page 11: ...Figure S 2 Charger circuit 9 ...
Page 13: ...Figure S 3 Line and Zero Crossing Detecting circuit 11 ...
Page 14: ...CH1 Line I P CH2 Q14 collector Figure W 2 Zero Crossing 12 ...
Page 16: ...Figure S 4 Inverter circuit 14 ...
Page 17: ...CH1 DS1 CH2 Output Voltage 1 200V Figure W 3 Inverter Circuit 1 15 ...
Page 18: ...CH1 DS2 CH2 Output Voltage 1 200 Figure W 4 Inverter Circuit 2 16 ...
Page 20: ...CH1 CLAMP OFF signal CH2 output voltage 1 200V Figure W 5 Clamp circuit 18 ...
Page 23: ...Figure S 5 CPU circuit 21 ...
Page 24: ...Figure S 6 Relay Circuit 22 ...
Page 25: ...CH1 C10 GND CH2 Output Voltage 1 200V Figure W 6 Relay speed up capacitor 23 ...
Page 27: ...Figure S 7 Panel circuit 25 ...
Page 33: ...Figure W 7 Battery mode examination flowchart Figure W 8 Line mode examination flowchart 30 ...