The rear view 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1.3 The 7 Pin Terminal Connecters Introduction Table 

Terminal Connectors 

Function 

Suggested Wire Gauge 

VO+   

Po) Voltage output 

At least #18AWG 

VO- 

 

Negative(-) Voltage output   

At least #18AWG 

SIG RTN   

Signal return 

At least #26AWG 

ON BATT   

Low when operation from utility 
line.   
Open when operating from battery. 

At least #26AWG 

REPLACE BATT 

Low when battery is charged. 
Open when battery fails the 
self-test. 

At least #26AWG 

BATT MISSING 

Low when battery is present. 
Open when battery is missing. 

At least #26AWG 

LOW BATT   

Low when battery is near full 
charge capacity. 
Open when operating from a 
battery with < 20% capacity. 

At least #26AWG 

 

 
 

AC input socket

TheAC input socket is
IEC320 C14.

                             DC output socket

TheDC outputincludes12VDCpower,
four dry contact signals and common
return point for these signals. Please
find the definensand wire connections
for DC output socket as below table.

Summary of Contents for DC UPS

Page 1: ...DC UPS User Manual ...

Page 2: ...on 3 1 3 The 7 Pin Terminal Connecters Introduction Table 4 2 Safety Information 5 3 Package Contents 6 4 Installation 7 9 4 1 Wire Connection 7 8 4 2 Wall Mounting Instructions Optional 9 5 Operation 10 6 Available Visual Alarms 11 7 Battery Replacement Procedure 12 8 Specifications 13 ...

Page 3: ...C 30W max output meets the major standard of network devices Integrated hot swappable to easy replacement battery allows battery replacement without power interruption Microprocessor controlled for optimized operation and maximum reliability Audible warning alarm with mute switch Outputs for remote monitoring On Battery Replace Battery Battery missing and Low battery alert Wall mountable design fo...

Page 4: ...ACE BATT Low when battery is charged Open when battery fails the self test At least 26AWG BATT MISSING Low when battery is present Open when battery is missing At least 26AWG LOW BATT Low when battery is near full charge capacity Open when operating from a battery with 20 capacity At least 26AWG AC input socket TheAC input socket is IEC320 C14 DC output socket TheDC outputincludes 12VDCpowe r four...

Page 5: ...e unit Refer repair issues only to qualified personnel Fuses or other parts must be replaced ONLY with parts of identical types and ratings Substitution of non identical parts can cause fire and other safety hazards All batteries used are sealed lead batteries Batteries should be recycled The battery charges when it is connected to the AC power The battery will fully charge during the first eight ...

Page 6: ...Package Contents The DC UPS package includes the following items Please inspect if there are any missing parts 1 x DC UPS Unit with 12V internal battery preinstalled 1 x User Manual 1 x 7 position connector ...

Page 7: ...ected 2 Plug IEC LOCAL power cord into the AC input socket on the back of DC UPS Do not connect the AC power cord to utility outlet prior to this process 3 Connect DC UPS to network device 3 1 If the telemetry cable is enclosed 1 Plug the telemetry cable into the 7 position connector 2 Then place the cable between the two sticks for fixing the cable as the following picture ...

Page 8: ...e that the correct wire gauges are used for the safety Please refer to 1 3 The 7 Pin Terminal Connecter Intro Table 2 Plug the 7 conductor cable into the outlet of the DC UPS 3 Then place the cable between the two sticks for fixing the cable as the following picture 4 Close the wire connection cover 5 Connect the other end of the cable to the equipment ...

Page 9: ...ions The distance between the centers of the 2 screws are 80cm STEP 2 Use a drill to drill holes where you made the mark on the wall If you drill into a wall stud proceed to Step 5 If not go to Step 4 STEP 3 Insert anchor s into the hole s STEP 4 Screw in the screw leaving it protruding 1 4 inch from the wall STEP 5 Mount the DC UPS on the screw heads Mounting holes 120mm 358mm 80mm Mounting holes...

Page 10: ...he battery Turn the mute switch ON then OFF then ON and OFF again within five seconds During the Self test the DC UPS operates in backup mode The DC UPS automatically conducts a Self test in two conditions 1 Operate it and then the MCU detects battery voltage is higher than 13V 2 Every 21 days while operating all the time Note During the self test the DC UPS briefly operates on battery backup powe...

Page 11: ... on battery power The alarm will stop when main power is returned Low Battery Yellow LED flashes one every 1 seconds The battery energy is running low This alarm will continue until the unit performs a forced shutdown when the battery is depleted Replace Battery Red LED flashes one every 2 seconds This alarm warns that the battery has reached the end of its useful life The user must replace the ba...

Page 12: ...tery from enclosure remove the wire connections from the battery STEP 3 Connect the new battery black to black red to red place the battery into the enclosure and then put the wires next by the battery inside of the closure as shown bellow WARNING Connect the correct color wires carefully to the corresponding terminals The battery has two color coded terminals red black as well as the two colors o...

Page 13: ... AC mode Green LED Lighting Backup mode Yellow LED Lighting Battery low Yellow LED Flashing Battery replace Red LED Flashing Battery missing Red LED Lighting Fault Red LED Lighting Battery self test Green LED flashing AUDIBLE ALARM Backup mode Sounding every 5 seconds Battery low Sounding every 1 second Battery replace Sounding every 2 seconds Battery missing Continuous sounding Fault Continuous s...

Reviews: