page 54
Ped
Pedestrian opening input
. (A normally-open potential-free input).
Momentarily connecting this input to Com will cause the gate to open to
the pedestrian open position. For more information refer to the
pedestrian feature in Section 21.
Trg
Trigger input
. (A normally-open potential-free input.) Momentarily
connecting this input to Com will cause the gate to open, close or stop,
depending on the operating mode selected. For more information see
the Autoclose feature and Modes of Operation.
Lck/Stp
Holiday Lockout or gate stop input
. (A normally-closed potential-
free input). For as long as a connection between this input and Com is
maintained the controller will behave normally, but when this
connection to Com is broken all inputs are inhibited.
If this input is enabled while the gate is moving or in the
open position, it will only activate and inhibit operation of all
the inputs when the gate is back in the closed position
This input can be configured as an emergency stop input.
Refer to Section 21, Menu 2 for details
If the Lck function is not required a link must be fitted
between Lck and Com*(refer to note on page 55)
Safety Open
Opening beam safety input
. (A normally-closed potential-free input).
As long as a connection between this input and Common is maintained
the controller will behave normally. When this connection is broken it
will prevent the gate from opening if it is stationary, and will stop and
close the gate if it is opening. This input has no effect if the gate is
closing.
If the Safety Open and reverse functions are not required a
link must be fitted between Safety Open and Safe Common
for the controller to operate normally*
(refer to note on page 55)
Safety Close
Closing beam safety input
. (A normally-closed potential-free input).
As long as a connection between this input and Common is maintained
the controller will behave normally. When this connection is broken it will
prevent the gate from closing if it is stationary, and will stop and open
the gate if it is closing. This input has no effect if the gate is opening.
If the Safety Close function is not required a link must be fitted
between Safety Close and Safe Common for the controller to
operate normally* (refer to note on page 55)
Aux 12V Out
Auxiliary power connection
. Pr12V DC supply for auxiliary
equipment such as a radio receiver, photo cells, etc. It is electronically limited
to 300A.