E l e c t r i c a l S p e c i f i c a t i o n s
Important –
Qualified and licensed electricians must perform all
electrical hookups. The following specifications must be followed in
order to ensure proper performance and safety.
WARNING:
Starting an incorrectly wired spa could cause
severe damage to the mechanical equipment or
even bodily harm. Have your licensed electrician
verify GFCI wiring with the schematics on pages 9-
11 prior to starting the spa or call the technical
support line at (727) 490-2239.
Caution:
Failure to abide by specifications listed may result in
damage to the equipment and will void the warranty.
US/Canada:
All spas must be wired with a 50 Amp breaker. Failure to do so will
cause equipment damage and will not be covered under your
warranty.
All spas must be protected with an over current protective device
with built-in GFCI in the service panel.
Voltage
/Freq.
Amp.
Phase
Breaker
Size
Amp/GFI
Wire size
Country
# of
terminals
on plug
240V
60Hz
40A
1
50A
6/3 with Ground
U.S. &
Canada
4
230V
50Hz
32A
1
1x40A
3x4 mm
2
European
Union
4
230V
50Hz
16A
2
2x20A
5x1.5mm
2
European
Union
5
230V
50Hz
16A
3
3x20A
5x1.5mm
2
European
Union
5
EUROPE:
WARNING:
Disconnect the electrical power before servicing.
Before obtaining access to terminals, all supply
circuits must be disconnected.
Avertissement:
Disconnecter du circuit d'alimentation
electrique avent l'entretien.