8.2 Barrier Status Function Output
The logic signalling of the feature is routed to a physical controller output based on
the setting specified in this menu. There are four physical controller outputs that are
available for output routing as shown below:
8.3 State Configuration
Each of the seven operating states can be independently configured to drive the output
active (ON) or inactive (OFF) according to the table below. The RAISING and LOWERING
states offer additional configuration options, allowing the output to transition to an active
or inactive state if the barrier is above or below a particular arc angle.
•
In the RAISING state, the output will start in the inactive state, and transition to the
active state if the barrier is at or above the specified arc angle
•
In the LOWERING state, the output will start in the active state, and transition to the
inactive state if the barrier is at or below the specified arc angle
1. The output will transition to the active state as soon as the barrier transitions to the RAISING state.
2. The arc angle is specified in degrees. The angle is measured with respect to the horizontal (0
°
),
increasing in the opening or raising direction of the barrier.
3. The output will transition to the active state as soon as the barrier transitions to the LOWERING state.
Menu 9 - Ticket Vendor Interlock (TVI) Output
The Ticket Vendor Interlock feature provides an interlocking mechanism between a ticket
vending machine, and the
SECTOR II
barrier.
In the interlock configuration, the ticket vending equipment activates the barrier when
a ticket for access is validly issued. The barrier now needs to interlock (prevent) further
tickets from being issued while the barrier is raised. The interlock expires when the
barrier reaches the closed position again.
TABLE 4
Output setting
on controller
Output
Description
Output
Type
Electrical Switch Characteristics
RLY
Relay
Dry Contact
24V DC/250V AC, 2A contact
XIO
Aux IO
Open Drain
Open Drain – 3A sink current, with a
3V floating terminal Voltage.
AUX
Aux Out
Open Drain
Open Drain – 3A sink current
LED
Status LED
Open Collector
Open Collector 5V – 50mA Source
Barrier State
Option
Barrier lowered
OFF
ON
Barrier raising
OFF
ON
1
5
°
, 10
°
, 15
°
, 20
°
,… 80
°
, 85
°
2
Barrier partly-raised
OFF
ON
Barrier raised
OFF
ON
Barrier lowering
OFF
ON
3
5
°
, 10
°
, 15
°
, 20
°
,… 80
°
, 85
°
Barrier partly-lowered
OFF
ON
Unknown indication
OFF
ON
TABLE 5
ADVANCED CONTROLLER SETUP
SECTION 7