C200 BOX CONTENTS CHECKLIST 

 

C200 Series UPS  

 

USB A to B  

 

Software CD 

 

Power lead 

 

Warranty Card 

 

Telephone patch lead 

 

Quick start guide 

 

 

INSTALLATION  

 

 

 

 

 

DO NOT 

connect the UPS to a mains supply until installation is completed 

 

Ventilation of the UPS is important for proper operation. Ensure the air vents on the front, side and rear of the 

UPS are clear. Allow adequate space around the UPS. The airflow diagram is shown as below: 

 

 

 

 

Installation considerations:  

 

 

The final location of the UPS unit must be on a flat stable surface in a well-ventilated environment 

 

DO 

keep at least 200mm of free space behind the rear panel

 

 

If installing an additional unit, place it next to the first unit in its final location 

 

 

DO 

allow the UPS to reach ambient temperature before turning on

 

 

The UPS needs to be fully charged to achieve full autonomy

 

 

 

 

IF ANY OF THE ITEMS ARE MISSING FROM THE UPS BOX PLEASE NOTIFY YOUR SUPPLIER  

 

DO NOT MAKE ANY UNLICENSED MODIFICATIONS TO THE UPS. THIS MAY INCUR DAMAGE AND AFFECT THE UPS 

WARRANTY. 

 

DO NOT FORGET TO REGISTER THE UPS WARRANTY 

WWW.CERTAUPS.COM/SUPPORT/WARRANTY-REGISTRATION/

 

 

 

Summary of Contents for C200 Series

Page 1: ...A COMPLETE INSTALLATION AND USER GUIDE THE C200 SERIES A line interactive uninterruptible power supply UPS solution available from 1000VA 2000VA www certaups com For assistance please contact your local CertaUPS partner ...

Page 2: ...S CHECKLIST 9 C200 SERIES STARTUP AND SHUTDOWN 10 STARTING THE UPS WITH MAIN POWER PRESENT 10 STARTING THE UPS FROM BATTERY 10 UPS SHUTDOWN WITH MAINS POWER 11 UPS SHUTDOWN WITHOUT MAINS POWER 11 USB COMMUNICATION PORT 12 SOFTWARE 12 UPS MAINTENACE 13 UPS CARE 13 TRANSPORTING THE UPS 13 STORING THE UPS 14 TECHNICAL DATA 15 ELECTRICAL SPECIFICATION 15 OPERATING ENVIROMENT 15 RUNTIMES 16 DIMENSIONS ...

Page 3: ...handling please ensure that the following precautions are taken QUALIFIED PERSONNEL Any persons servicing the UPS must be qualified and knowledgeable in UPS technology and batteries CLOTHING Correct PPE should always be worn POWER OFF Ensure all mains power is disconnected before starting work TOOLS always use insulated tools Do not lay tools down near the UPS or batteries Follow all isolation pro...

Page 4: ...hey appear within this manual DO check that the indicators on the rating plate correspond to the AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS DO ensure the outlet is installed near the UPS and is easily accessible DO store the UPS in a dry environment DO keep the UPS in a well ventilated area Additional considerations The UPS outputs ar...

Page 5: ...y model Single Phase input Single Phase output THE TECHNOLOGY The C200 UPS series uses line interactive VI Voltage Independent technology which performs in a similar way to an offline UPS A line interactive solution includes a voltage regulator which maintains the inverter and redirects the DC supply When the mains power fails or fluctuates the load is transferred to the inverter output This type ...

Page 6: ...ied operating temperatures and remain within these guidelines To achieve the battery design life it is not recommended for the ambient temperature to exceed 25 degrees Celsius Unpacking the unit in a low temperature environment may cause condensation to occur in and on the device DO NOT install the UPS EBM until the inside and outside of the device are clear of condensation Unpack the equipment an...

Page 7: ...erations The final location of the UPS unit must be on a flat stable surface in a well ventilated environment DO keep at least 200mm of free space behind the rear panel If installing an additional unit place it next to the first unit in its final location DO allow the UPS to reach ambient temperature before turning on The UPS needs to be fully charged to achieve full autonomy IF ANY OF THE ITEMS A...

Page 8: ...s through PC STEP SIX Software Installation 1 Please download the monitoring and shutdown software from the website www certaups com downloads to download ViewPower software 2 When your computer restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock STEP SEVEN Power On Off UPS Press power switch on the front panel of the UPS to turn on the UPS...

Page 9: ...AC supply to any connected equipment 4 Whilst operating in battery mode the unit beep once every 10 seconds to alert the user to a mains AC failure UPS SHUTDOWN WITH MAINS POWER To shutdown the UPS with mains power 1 Press the button to shut the unit down 2 After that the UPS will transfer to standby mode immediately 1 In order to cut off the UPS output remove the mains power supply A few seconds ...

Page 10: ... management software tool Key features Allows control and monitoring of multiple UPSs via LAN and INTERNET User friendly power analysis graph event statistics history data chart export Real time dynamic graphs of UPS data voltage frequency load level battery level Safely OS shutdown and protection from data loss during power failure Warning notifications via audible alarm broadcast mobile messenge...

Page 11: ...lowing procedure should be performed or supervised by personnel knowledgeable about batteries and the required precautions Keep unauthorised personnel away from batteries If the UPS requires any type of transportation the batteries must be disconnected but not removed before the unit is transported Verify that the UPS is off and disconnected from mains power Place the UPS on a flat stable surface ...

Page 12: ...on EVENT CAUSE ACTION Nothing displays on the front panel Low battery Battery fault The UPS is not turned on Charge the UPS for at least 6 hours Replace the battery with the same battery type Press the power switch again to turn the UPS on Alarm continuously sounds when the mains is normal The UPS is overloaded Remove some load first Before reconnecting the equipment verify that the load meets the...

Page 13: ...capacity PHYSICAL Dimension WxDxH mm 350 x 146 x 160 397 x 146 x 205 Net Weight KG 8 96 12 18 13 7 OPERATING ENVIRONMENT Ambient Temperature 0 C to 40 C Full load no de rating 40 C to50 C output power derated to 50 load Charger current derated 50 20 C to 25 C recommended operating range for peak performance and lifespan Operating humidity 95 no condensing Altitude 3000m 3000m Above 3000m altitude1...

Page 14: ...el No Dimensions W H D mm Net Weight kg C200 1000 350 x 146 x 160 8 96 C200 1500 397 x 146 x 205 12 18 C200 2000 397 x 146 x 205 13 7 A FULL GLOSSARY OF TERMS CAN BE FOUND AT WWW CERTAUPS COM SUPPORT UPS GLOSSARY FOR FURTHER INFORMATION OR ASSISTANCE PLEASE CONTACT YOUR CertaUPS REPRESENTATIVE OR VISIT WWW CERTAUPS COM ...