4.1 Inspection
Inspect the packaging and its contents for damage, inform the courier immediately
should you find signs of damage. Keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feed is isolated and secured to prevent it from
being switched back on again.
4.2 Connection
UPS input connection
If the UPS is connected via the power cord please use a correctly isolated and fused
socket. The user can refer to the table below. If the UPS is hard-wired it is
recommended to select the 2.5mm
2
cable and the “GND” terminal should be
grounded first. The UPS System has no input breaker on the standard cabinet.
When installing the UPS the user needs to connect the external breakers and
protective components in the input supply. It is recommended to select an isolator
instead of the traditional combination kit including breaker and fuse. When
selecting the ISOLATOR the user can refer to below table.
Model No.
UPS input isolator
VOLTAGE
CURRENT
C400R-010-B (C)
300Vac
10A
C400R-020-B (C)
300Vac
16A
C400R-030-B (C)
300Vac
20A
UPS output connection
The output of the UPS uses IEC socket-types, IEC320 C13 for 10A load, IEC320
C19 for 16A load. Simply plug the load power cord to the output sockets to complete
connection.
Model no.
Output socket (pcs)
C400R-010-B (C) / C400R-020-B (C)
8 * IEC320 C13
C400R-030-B (C)
8 * IEC320 C13 + 1 * C19