8.3 Battery replacement
If the battery service life has been exceeded the batteries must be replaced
to maintain reliable operation. Battery replacement should be performed
only by qualified personnel. Shut off the UPS completely before
replacement. If there is a battery breaker, turn it off first. Disconnect the
battery cable carefully and make sure no any exposed wires can be touched
or short. Reconnect the new batteries to the UPS by following section 5.8.
Then turn on the battery breaker and start the UPS.
If batteries need to be replaced while the UPS is running while making sure
the UPS will not shutdown during the replacement. First if there is a battery
breaker then turn it off first. Disconnect the battery cable carefully and make
sure no exposed wires can be touched. Reconnect the new batteries to the
UPS by following section 5.8. Then turn on the battery breaker and press the
ON switch to make the UPS perform a battery test, check whether the
battery status is normal.
9. Technical data
9.1
Electrical specifications
INPUT
Model No.
C400R-010-B(C)
C400R-020-B(C)
C400R-030-B(C)
Phase
1
Frequency
(45~55)/(54~66) Hz
Max Current(A)
7.5
13.5
16
OUTPUT
Model No.
C400R-010-B(C)
C400R-020-B(C)
C400R-030-B(C)
Power rating
1000VA/9000kW
2000VA/8000W
3000VA/7000W
Voltage
208/220/230/240× (1±1%) VAC
Frequency
50/60 (±0.2) Hz (Battery mode)