Table 10-1 Dry out/in contacts
Dry out signal
Description
Summary Alarm
Activated when any warning happens
On Battery
Activated when the UPS operates on battery
Battery Low
Activated by the battery low alarm
UPS OK
Activated when the UPS has no alarms and no fault.
On Bypass
Activated when the UPS is in bypass.
Dry in signal
Description
Disable
Disable the function.
UPS On
One second pulse activate, if active, the UPS turns on
when UPS is not on inverter. It is the same as a remote
button to control UPS status.
UPS Off
One second pulse activate, if active, the UPS turns off
when UPS is on inverter. It is the same as a remote
button to control UPS status.
Maintain bypass
One second pulse activate, if active, the UPS will
transfer to bypass mode. To recover to a normal status,
first make the signal inactive, then the UPS needs to be
turned on by manual operation.