Emergency supply
period shorter than
nominal value
Batteries are not fully charged /
batteries defect
Charge the batteries for at least 12 hours and then check capacity.
8.2
SILENCING THE ALARM
•
Press the ESC (Escape) button on the front panel display for 2 Seconds to silence the alarm.
Check the alarm condition and perform the applicable action to resolve the condition.
If an alarm status changes the alarm will need to be silenced again.
9.
TECHNICAL DATA
9.1
BLOCK DIAGRAM
9.2
UPS SPECIFICATION
Tower UPS
Model
C650-060-B
C650-060-C
C650-100-B
C650-100-C
Capacity
6kVA/6kW
10kVA / 10kW
INPUT
Input Voltage Range
110VAC - 276VAC
Rated Voltage
220/230/240VAC
Frequency
50Hz/60Hz
Frequency Range
45Hz-55Hz (50Hz system), 54Hz-66Hz (60Hz system) @ load>60%
Power Factor
1
Rated current (20pcs battery)
35A
45A
54A
63A
OUTPUT
Voltage Regulation (AC Mode)
220/230/240V AC
Rated Frequency
50 Hz / 60 Hz
Power Factor
1
Voltage accuracy
±1%