59
8. Troubleshooting
The online series UPS is designed for durable, automatic operation and
issues alarms to alert you whenever potential operating problems occur.
Usually the alarms shown by the control panel do not mean that the
output power is affected. Instead, they are preventive alarms intended to
alert the user. Active alarms are accompanied by an audible buzzer.
The control panel provides troubleshooting information from two main
menus:
UPS status menu: Access to all active alarms
Event Log menu: Access to the most recent 50 events, which may
include active and closed alarms
8.1 Typical Alarms and Conditions
Alarm or Condition
Possible cause
Action
ON Maintenance
Bypass
Alarm Code: 72
UPS was manually
commanded to switch to
bypass and will remain in
bypass until commanded
out of bypass
Check the maintain bypass
switch status
In Battery Mode
Alarm Code: 62
A utility failure has
occurred and the UPS is in
Battery mode.
The UPS is powering the
equipment with battery power.
Prepare your equipment for
shutdown.
In Eco Mode
Alarm Code: 63
The UPS is on bypass while
operating on the High
Efficiency setting.
The equipment transferred to
bypass utility power as a
normal function of High
Efficiency operation. Battery
mode is available and your
equipment is protected.
Epo Active
Alarm Code: 71
The external contacts in
the rear of the UPS are
configured for REPO
operation and they have
been activated.
Check the EPO connector status