60
Site Wiring Fault
Alarm Code: 04
Site Fault detection is
supported on all models
anytime there is a
Grounding Neutral
connection.
Alarm triggers when the
difference between ground
and neutral voltage is >
15v.
Site Fault detection should be
enabled by default. It can still
be enabled / disabled from the
LCD settings menu.
Reconnect all input wires
Utility Abnormal
Alarm Code: 02
Utility is out of the
tolerance of input
Check input mains condition
Back feed
Alarm Code:93
UPS has a unexpected
bypass current on battery
mode
Transfer to maintenance bypass
and call service.
Battery Disconnect
Alarm Code:11
Battery voltage is lower
than the batteries
disconnected level defined
for this UPS. This may be
due to a blown fuse,
intermittent battery
connection or battery
cable being disconnected.
Verify that all batteries are
properly connected.
If the condition persists,
contact your service
representative.
Battery low
Alarm Code:12
The UPS is in Battery mode
and the battery is running
low
This warning is approximate,
and the actual time to
shutdown may vary
significantly.
Depending on the UPS load and
number of Extended Battery
Modules(EBMs), the “Battery
Low” warning may occur before
the batteries reach 25%
capacity
Service Battery
Alarm Code:13
A faulted battery string has
been detected and as a
result the battery charger
has been disabled until it is
replaced
Contact your service
representative
Output Overload
Output is overload.
Remove some of the