16
MB Pool & spa heater
PLUMBING FOR WATER CONNECTIONS
LEFT SIDE WATER CONNECTION CONVERSION
185, 265 & 405 Models Only
There are two ways of achieving the connection conversion. Removal and turning of the heat
exchanger or, swapping of the headers. Generally swapping headers is easier and this process is
described here.
1. Remove the right and left side access panels (Fig.1 & 2)
2. Withdraw the temperature and overheat sensors from their pockets (beware of the heatsink compound)
and disconnect the connections to the pressure switch and the overheat thermostat.
3. Re-route the sensors and cables to the other side.
4. Remove the 12 bolts holding the Headers to their respective tubesheets.
5. Clean the mating surfaces for the header gaskets and the gaskets themselves.
(NB. Use only silicone grease as a lubricant)
6
Fit the headers on their new sides ensuring they are square and correctly compressing the gasket.
7. Refi t the sensors and connectors to the safety devices.
8. Re-commission and check for leaks.
9. Replace the side access panels.
Fig. 1
Fig. 2