Cessna 170 Service Manual
Electrical System
7
generator. Therefore, it is important that both generator and regulator be of the same capacity to obtain best
performance without damage.
TROUBLESHOOTING THE GENERATOR/REGULATOR SYSTEM
NO CHARGE INDICATED ON AMMETER
. If the charging circuit does not indicate a charge or if the
ammeter indicates the generator is not producing current at normal cruising RPM, the trouble can be
isolated without special tools or instrumentation. First determine that no obvious difficulty exists with the
system wiring, i.e., that the generator ARMature terminal (large one) and the generator FieLD terminal ends
are secure with no broken wires. Also check at the voltage regulator BATtery, ARMature, and FieLD
terminals that the wiring is secure, terminals are tight and that no wires are broken. Confirm that the voltage
regulator base is grounded to the firewall and that the rubber shock mounts do not insulate it from achieving
such a ground (ground strap is secure.) Confirm the generator fuse or circuit breaker is good and/or reset.
If none of these items are defective, then using a small jumper wire, MOMENTARILY connect the voltage
regulator ARMature terminal to it’s BATtery terminal while the Master switch is ON, but the engine NOT
RUNNING. This will insure that the generator and voltage regulator is polarized. Start the engine and run it
at approx. 2,000 RPM and observe if the generator is now charging.
If the generator still does not charge, then shut down the engine and with a small jumper wire connect the
generator FieLD terminal (small one) directly to ground and then start the engine and run it at 2,000 RPM.
If the generator still does not produce a current then the generator is defective and should be removed and
repaired, overhauled, or exchanged with a serviceable one.
If the generator DID produce a charge then the fault lies with the voltage regulator or the aircraft wiring
system. Next, remove the small test jumper wire from the generator FieLD terminal, and use it to connect
the Voltage REGULATOR CASE to ground as in Appdx. EL-Fig.EL-09, TEST 1 (Confirm Regulator Ground.)
Again run the engine at approx. 2,000 RPM and observe if the generator is now charging. Is so, then the
problem is a faulty regulator ground. Repair the regulator ground connection between the reg. case and
aircraft ground. If there was STILL NO CHARGE, then connect the small test jumper from the regulator
FieLD terminal to ground as in Appdx. EL, Fig. EL-09, TEST 2 (Isolate Regulator.) Start the engine and run
it at 2,000 RPM and if the generator now produces a charge then the fault lies with the voltage regulator and
it must be repaired, overhauled, or replaced. However, it there is STILL NO CHARGE then connect a small
test jumper wire between the ARMature and BATtery terminals of the voltage regulator as illustrated in
Appdx. EL, Fig EL-09, TEST 3 (Cut Out Relay.) This shorts out the Reverse Current Relay and the Current
Regulating Relay and connects the regulator directly to the battery. Run the engine again at approx. 2,000
RPM and if a charge now occurs the voltage regulator is still at fault and must be replaced, overhauled, or
repaired.
If the generator STILL did not produce a charge, then the fault lies with the aircraft wiring and/or master
switch. Use a jumper wire to connect the generator FieLD terminal directly to the voltage regulator FieLD
terminal. Again, start the engine and run it at 2,000 RPM, and if the generator now produces a charge then
the fault lies in the generator-to-master switch-to-Voltage regulator FieLD circuit. This may be due to a
faulty Master switch.
Check the wiring at the cockpit master switch terminals for continuity when the switch is actuated.
Remember that there are four terminals at the master switch. Two are used to connect the battery solenoid
(relay) to ground, and the other two (the ones we’re interested in here) connect the generator FieLD terminal
to the voltage regulator FieLD terminal. Confirm this circuit makes continuity across those two terminals
when the switch is activated. If found defective, repair or replace that switch and its associated wiring.
GENERATOR TESTS, REPAIRS AND ADJUSTMENTS.
There is very little to go wrong with the Delco-
Remy generators if they are polarized and have not suffered mechanical failure such as damage from a
leaking oil seal, or failed brushes or bearings resulting in contact between the armature and the field pole
shoes, or burned windings from failed or incorrect regulator. Inspecting the generator in-situ is a simple
process and may be done with the engine cowling removed. Remove the blast-tube/brush shield-cover to
examine the brushes. When new the brushes are approximately three-quarters inch long. When the
brushes are more than half worn, they should be replaced. It is best to replace them on the workbench.
Remove the generator in accordance with the previous instructions. Examine for evidence of oil
contamination. Using a screwdriver, pry the brush holders away from the commutator and prop them in that
position with a wooden stick or tongue depressors. Be careful not to damage the brushes if they are not to
be replaced. Examine for rough or worn bearings by spinning the armature by hand and listening and/or
feeling for roughness, grinding, or points of increased friction. Remove the brush end-plate by removing the
long generator thru-bolts. Replace the brushes at this time if desired. Be certain that brush leads do not
ground against the case or springs. This is also the time to remove the armature and inspect, and/or
replace the bearings and oil seal.
Summary of Contents for 170
Page 3: ...Cessna 170 Service Manual Electrical System ELECTRICAL ...
Page 25: ...Cessna 170 Service Manual Electrical System ELECTRICAL SCHEMATIC SNs 20267 THRU 25372 ...
Page 26: ...Cessna 170 Service Manual Electrical System ELECTRICAL SCHEMATIC SNs 25373 THRU 26995 ...
Page 27: ...Cessna 170 Service Manual Electrical System ELECTRICAL SCHEMATIC SNs 26996 AND ON ...
Page 29: ...Cessna 170 Manual Electrical System ...
Page 30: ...Cessna 170 Manual Electrical System ...
Page 31: ...Cessna 170 Manual Electrical System ...
Page 32: ...Cessna 170 Manual Electrical System ...
Page 33: ...Cessna 170 Service Manual Electrical System ...
Page 34: ...Cessna 170 Service Manual Electrical System ...
Page 42: ......