CET Electric Technology
22
Figure 3-4 Setup Menu
3.1.3.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Description
Range
Default
Menu
1
st
2
nd
3
rd
Password
Enter Password
0000 to 9999
0000
Basic
Wiring Mode
Meter’s Wiring Connection
DEMO/
1P2W L-N/1P2W L-L/
1P3W/3P3W/3P4W
3P4W
PT Primary
PT Primary Ratio
1 to 1000000V
100V
PT Secondary
PT Secondary Ratio
1 to 690V
100V
CT Primary
CT Primary Ratio
1 to 30000A
5A
CT Secondary
CT Secondary Ratio
1 to 5A
5A
I4 Primary*
I4 Primary Ratio
1 to 30000A
5A
I4 Secondary*
I4 Secondary Ratio
1 to 5A
5A
PF Convention
PF Convention
IEC/IEEE/-IEEE
1
IEC
kVA Calc.
kVA Calculation Method
Vector/Scalar
2
Vector
I1 Polarity
I1 Polarity
Normal/Reverse
Normal
I2 Polarity
I2 Polarity
I3 Polarity
I3 Polarity
THD Calc.
Select between
% of Fundamental or % of
RMS
THDf/THDr
3
THDf
DMD Period
Demand Interval
1 to 60 min
15
No. of Windows
Number of Sliding Windows
1 to 15
1
Predicted Resp.
Predicted Response
70 to 99
70