CET Electric Technology
60
1102
RW
kWh Export
INT32
1104
RW
kvarh Import
INT32
kvarh
1106
RW
kvarh Export
INT32
1108
RW
kVAh
INT32
kVAh
Table 5-8 Interval Energy Measurements
Note:
1)
The EN Period (Register# 6047) determines how long the Interval Energy Measurements will be updated. For example, if
EN Period = 60 min, the Interval Energy Measurements will be refreshed hourly on the hour.
5.3 DI Pulse Counters
Register
Property
Description
Format
Range/Unit
1200
RW
DI1 Pulse Counter
UINT32
0 to 1,000,000,000
DI Pulse Counter = Pulse Counter
x DI Pulse Weight
1202
RW
DI2 Pulse Counter
UINT32
1204
RW
DI3 Pulse Counter
UINT32
1206
RW
DI4 Pulse Counter
UINT32
Table 5-9 DI Pulse Counter
5.4 Power Quality Measurements
5.4.1 Basic PQ Measurements
Register
Property
Description
Format
Scale
Unit
1300
RO
Ia TDD
Float
x1
%
(0.1 means
10%)
1302
RO
Ib TDD
Float
1304
RO
Ic TDD
Float
1306
RO
Ia TDD Odd
Float
1308
RO
Ib TDD Odd
Float
1310
RO
Ic TDD Odd
Float
1312
RO
Ia TDD Even
Float
1314
RO
Ib TDD Even
Float
1316
RO
Ic TDD Even
Float
1318
RO
Ia K-Factor
Float
-
1320
RO
Ib K-Factor
Float
1322
RO
Ic K-Factor
Float
1324
RO
Ia Crest Factor
Float
1326
RO
Ib Crest Factor
Float
1328
RO
Ic Crest Factor
Float
1330
RO
Voltage Unbalance
Float
1332
RO
Current Unbalance
Float
Table 5-10 Power Quality Measurements
5.4.2 Current Harmonic Measurements
Register
Property
Description
Format
Scale
Unit
1400
RO
Ia THD
Float
x1
%
(0.1 means 10%)
1402
RO
Ib THD
Float
1404
RO
Ic THD
Float
1406
RO
Ia TOHD
Float
1408
RO
Ib TOHD
Float
1410
RO
Ic TOHD
Float
1412
RO
Ia TEHD
Float
1414
RO
Ib TEHD
Float
1416
RO
Ic TEHD
Float
1418
RO
Ia HD02
Float
1420
RO
Ib HD02
Float
1422
RO
Ic HD02
Float
1424~1590
RO
…
Float
1592
RO
Ia HD31
Float
1594
RO
Ib HD31
Float
1596
RO
Ic HD31
Float
Table 5-11 Current Harmonic Measurements