CET Electric Technology
66
5146~5151
RO
Ic Crest Factor
5152~5157
RO
Voltage Unbalance
5158~5163
RO
Current Unbalance
5164~5169
RO
I4
x1
A
5170~5175
RO
Ir (Residual Current)
Table 5-21 Min Log of Last Month (Before Last Reset)
5.6.5 Max/Min Log Structure
Offset
Description
+0
High
Year - 2000
Low
Month
+1
High
Day
Low
Hour
+2
High
Minute
Low
Second
+3
-
Millisecond
+4~+5
-
Max/Min Value
Table 5-22 Max/Min Structure
5.7 Monthly Energy Log
Register
Property
Description
Format
Scale
Unit
0980
RW
Month
1
INT16
0* to 12
0981
RO
High-order Byte: Year (0-99)
Low-order Byte: Month (1-12)
INT16
Time Stamp
(20YY/MM/DD
HH:MM:SS)
0982
RO
High-order Byte: Day (1-31)
Low-order Byte: Hour (0-23)
INT16
0983
RO
High-order Byte: Minute (0-59)
Low-order Byte: Second (0-59)
INT16
0984
RW
kWh Import
INT32
x0.1
kWh
0986
RW
kWh Export
INT32
0988
RO
kWh Net
INT32
0990
RO
kWh Total
INT32
0992
RW
kvarh Import
INT32
x0.1
kvarh
0994
RW
kvarh Export
INT32
0996
RO
kvarh Net
INT32
0998
RO
kvarh Total
INT32
1000
RW
kVAh
INT32
x0.1
kVAh
1002
RW
kvarh Q1
INT32
x0.1
kvarh
1004
RW
kvarh Q2
INT32
1006
RW
kvarh Q3
INT32
1008
RW
kvarh Q4
INT32
1010
RW
kWh Import of T1
INT32
x0.1
kWh
1012
RW
kWh Export of T1
INT32
1014
RW
kvarh Import of T1
INT32
x0.1
kvarh
1016
RW
kvarh Export of T1
INT32
1018
RW
kVAh of T1
INT32
x0.1
kVAh
1020
RW
kWh Import of T2
INT32
x0.1
kWh
1022
RW
kWh Export of T2
INT32
1024
RW
kvarh Import of T2
INT32
x0.1
kvarh
1026
RW
kvarh Export of T2
INT32
1028
RW
kVAh of T2
INT32
x0.1
kVAh
1030
RW
kWh Import of T3
INT32
x0.1
kWh
1032
RW
kWh Export of T3
INT32
1034
RW
kvarh Import of T3
INT32
x0.1
kvarh
1036
RW
kvarh Export of T3
INT32
1038
RW
kVAh of T3
INT32
x0.1
kVAh
1040
RW
kWh Import of T4
INT32
x0.1
kWh
1042
RW
kWh Export of T4
INT32
1044
RW
kvarh Import of T4
INT32
x0.1
kvarh
1046
RW
kvarh Export of T4
INT32
1048
RW
kVAh of T4
INT32
x0.1
kVAh
1050
RW
kWh Import of T5
INT32
x0.1
kWh
1052
RW
kWh Export of T5
INT32
1054
RW
kvarh Import of T5
INT32
x0.1
kvarh
1056
RW
kvarh Export of T5
INT32