CET Electric Technology
71
Table 5-29 SOE Event Classification
Notes:
1)
Clear Present Energy via Panel means to clear 3-Phase Total Energy registers, Phase A/B/C Energy registers (including TOU
Energy & Interval Energy), and Monthly Energy Log of the Present Month.
2)
Clear Historical Monthly Energy Log via Panel means to clear the Monthly Energy Log of the last 1 to 12 months, excluding
the Monthly Energy Log for the Present Month.
3)
Clear All Data via Front Panel or Communication means to clear 3-Phase Total Energy registers, Phase A/B/C Energy
registers, Monthly Energy Log of the Present Month, All Peak Demands, All Max/Min Logs, Device Operating Time, All DI
Pulse Counters, All DR Logs and All Freeze Logs.
4)
Clear All Energy Registers via Communications means to clear the 3-Ø Total and Per-Phase energy registers (including TOU
Energy & Interval Energy).
5)
Clear Present Monthly Energy Log via Communications means to clear the Monthly Energy Log of the Present Month.
6)
Clear Historical Monthly Energy Log via Communications means to clear Monthly Energy Log of the last 1 to 12 months,
excluding the Monthly Energy Log for the Present Month
7)
The event values of Switch TOU Schedule are illustrated in the table below:
Record Value
Description
1
Switch Schedule 1 to Schedule 2 manually
2
Switch Schedule 2 to Schedule 1 manually
3
Switch Schedule 1 to Schedule 2 automatically
4
Switch Schedule 2 to Schedule 1 automatically
Table 5-30 TOU Switch Records
9
0
0
Clear All Data via Front Panel
3
10
0
0
Clear SOE Log via Front Panel
11
0
x=1 to 4
Clear DIx Pulse Counter via Front Panel
12
0
0
Clear All Pulse Counter via Front Panel
13
0
0
Clear Device Operating Time via Front
Panel
14
0
0
Set Clock via Front Panel
15
0
0
Setup Changed via Front Panel
16~17
0
…
Reserved
18
0
0
Restore Factory via Front Panel
19~29
0
…
Reserved
30
0
0
Clear All Energy Registers via
Communications
4
31
0
0
Clear Present Monthly Energy Log via
Communications
5
32
0
0
Clear Historical Monthly Energy log via
Communications
6
33
0
0
Clear Peak Demand of
This Month (Since Last Reset) via
Communications
34
0
0
Clear All Demand Registers via
Communications
35
0
0
Clear Max./Min. Logs of This Month
(Since Last Reset) via Communications
36
0
0
Clear All Max/Min Logs via
Communications
37
0
0
Clear All Data via Communications
3
38
0
0
Clear SOE Log via Communications
39
0
x=1 to 4
Clear DIx Pulse Counter via
Communications
40
0
0
Clear All DI Pulse Counters via
Communications
41
0
0
Clear Device Operating Time via
Communications
42
0
0
Restore Factory via Communications
43
0
0
Setup Changes via Communications
44
0
0
Preset Energy Value via Communications
45
0
0
Setup TOU Energy via Communications
46
0
1~4
Switch TOU Schedule
7
47
0
1~5
Clear DRx Log via Communications
48
0
0
Clear All DR logs via Communications
49
Clear Daily Freeze Log via
Communications
50
Clear Monthly Freeze Log via
Communication
6 Alarm Email
1
0
0
Setpoint Trigger Alarm Email