CET Electric Technology
88
R
Database_Revision
0
R
Local_Time
Configuration by
timing
12:00:00:00
R
Local_Date
Configuration by
timing
2016.07.01
*
R = Read Only; R/W = Read/Write
Notes:
1)
Supported services:
o
ReadProperty
o
ReadPropertyMultiple
o
WriteProperty
o
TimeSynchronization
o
Who-Has
o
Who-Is, I-Am, I-Have
2)
Supported object types:
o
Analog-Input
o
Analog-Value
o
Binary-Input
o
Binary-Output
o
Device
3)
Analog Input Objects (PMC-53A-E’s Real-Time Parameters)
Optional Properties Supported: Description, Reliability
Use the Present_Value property of the Analog_Input objects for all read-only numeric variables
in PMC-53A-E. These objects support the Description and Reliability optional properties and all
required Analog_Input object properties. None of them are writable. The values that are not
instantaneous (i.e. Accumulated Energy, Peak Demand) are non-volatile.
Register
Description
Property
Unit
Range
AI 0000
Uan
1
R
V
AI 0002
Ubn
1
R
AI 0004
Ucn
1
R
AI 0006
ULN average
1
R
AI 0008
Uab
R
AI 0010
Ubc
R
AI 0012
Uca
R
AI 0014
ULL average
R
AI 0016
Ia
R
A
AI 0018
Ib
R
AI 0020
Ic
R
AI 0022
I average
R
AI 0024
kWa
1
R
kW
AI 0026
kWb
1
R
AI 0028
kWc
1
R
AI 0030
kW Total
R
AI 0032
kvara
1
R
kvar
AI 0034
kvarb
1
R
AI 0036
kvarc
1
R
AI 0038
kvar Total
R
AI 0040
kVAa
1
R
kVA
AI 0042
kVAb
1
R
AI 0044
kVAc
1
R
AI 0046
kVA Total
R
AI 0048
PFa
1
R
0 to 1
AI 0050
PFb
1
R
AI 0052
PFc
1
R
AI 0054
PF Total
R
AI 0056
Frequency
R
Hz
AI 0070
Neutral Current (Calculated)
R
A
AI 0072
I4 (Optional Measurement)
R
A
AI 0082
AI
R
AI 0084
Ir
R
A
AI 0500
kWh Import
R
kWh
0 to