CET Electric Technology
89
AI 0502
kWh Export
R
99999999.9
AI 0504
kWh Net
R
AI 0506
kWh Total
R
AI 0508
kvarh Import*
R
kvarh
AI 0510
kvarh Export*
R
AI 0512
kvarh Net*
R
AI 0514
kvarh Total*
R
AI 0516
kVAh*
R
kWh
AI 3006
kW Total Demand
R
kW
AI 3008
kvar Total Demand
R
kvar
AI 3010
kVA Total Demand
R
kVA
AI 3000
Ia Demand
R
A
AI 3002
Ib Demand
R
AI 3004
Ic Demand
R
AI 3418
kW Total Peak Demand
R
kW
AI 3424
kvar Total Peak Demand
R
kvar
AI 3430
kVA Total Peak Demand
R
kVA
AI 3400
Ia Peak Demand
R
A
AI 3406
Ib Peak Demand
R
AI 3412
Ic Peak Demand
R
AI 1600
Uan THD
2
R
%
AI 1602
Ubn THD
2
R
AI 1604
Ucn THD
2
R
AI 1400
Ia THD
R
AI 1402
Ib THD
R
AI 1404
Ic THD
R
AI 1318
Ia K Factor
R
AI 1320
Ib K Factor
R
AI 1322
Ic K Factor
R
AI 1300
Ia TDD
R
AI 1302
Ib TDD
R
AI 1304
Ic TDD
R
AI 1324
Ia Crest Factor
R
AI 1326
Ib Crest Factor
R
AI 1328
Ic Crest Factor
R
AI 1330
U Unbalance
R
AI 1332
I Unbalance
R
AI 0074
dPFa
1
R
-
0 to 1
AI 0076
dPFb
1
R
AI 0078
dPFc
1
R
AI 0058
Uan Angle
3
R
°
AI 0060
Ubn Angle
3
R
AI 0062
Ucn Angle
3
R
AI 0064
Ia Angle
R
AI 0066
Ib Angle
R
AI 0068
Ic Angle
R
AI 0104
Operating Time
R
h
AI 0526
Interval kWh Import
R
kWh
0 to
99999999.9
AI 0528
Interval kWh Export
R
AI 0530
Interval kvarh Import*
R
kvarh
AI 0532
Interval kvarh Export*
R
AI 0534
Interval kVAh*
R
kWh
AI 1200
DI #1 Counter
R
-
0 to
999,999,999
AI 1202
DI #2 Counter
R
AI 1204
DI #3 Counter
R
AI 1206
DI #4 Counter
R
*There are no unit types for kvarh and kVAh in BACnet so the return values are in unit of kWh.
Notes:
1)
When the Wiring Mode is 3P3W, the per phase line-to-neutral voltages, kWs, kvars, kVAs and
PFs have no meaning, and their registers are reserved.
2)
Uan/Ubn/Ucn THD = Uab/Ubc/Uca THD in 3P3W Wiring Mode and represent the harmonics
of the line voltages.
3)
Uan/Ubn/Ucn Angle = Uab/Ubc/Uca Angle in 3P3W Wiring Mode and represent the phase
angles of the line voltages.