4.4 Setpoints
The PMC-53A-E comes standard with 9 user programmable Setpoints which provide extensive control
by allowing a user to initiate an action in response to a specific condition. Typical setpoint applications
include alarming, fault detection and power quality monitoring.
Figure 4-1 Over Setpoint
Figure 4-2 Under Setpoint
Setpoints can be programmed via the Front Panel or through communications and have the following
setup parameters:
Setup Parameter
Definition
Options/Default*
Setpoint Type
Over or Under Setpoint.
0=Over Setpoint*
1=Under Setpoint
Setpoint
Parameter
Specify the parameter to be monitored.
See Table 4-7
Over Limit
Specify the value that the setpoint parameter must exceed
for Over Setpoint to become active or for Under Setpoint
to become inactive.
0*