Additional Front Panel Setup Parameters for BACnet MS/TP
The following BACnet MS/TP setup parameters should be configured via the PMC-53A-E’s Front
Panel before connecting the PMC-53A-E to a BACnet MS/TP network.
Parameters
Description
Option/Range
Default
MAC
MS/TP ID
^
0 to127
100
INST
Object Identifier
#
0 to 4194302
26001
MAXMAS
Maximum Number of Master
0 to 127
127
LOCK
Disable communication
YES/NO
NO
BAUD
Baud rate
1200/2400/4800/9600/19200/38400
9600
CONFIG
Comm. Port Configuration
8N1/8E1/8O1/8N2/8E2/8O2
8E1
^
The MS/TP ID is similar to the Modbus unit ID conceptually
#
The Object Identifier is similar to the IP address of an Ethernet network conceptually and is required to be
unique within the entire BACnet network