MAXI Cooling 

Operating instructions 

  

4 Feb 2019 

Page 2 of 2 

secondary circuits may lead to corrosion in the 
system. This type of system should be filled as 
infrequently as possible

If a fault develops, contact a skilled service 
technician. For information about suitable ser-
vice companies, contact your energy supplier. 

Only authorised personnel may work on the 
system. 

See important warnings:.

Troubleshooting chart 

Symptom

 

Cause

 

Action

 

Secondary system tem-
perature too high or too low  

Automatic control may need 
adjusting 

The control centre can be 
adjusted. See separate 
instructions 

Not enough cold coming 
from the system 

Circulation pump not running 

Check that the power is on and 
that the fuses are OK. 

Not enough water in the 
system 

Top up the system 

Air pockets in the heat 
exchanger or in the secondary 
circuit 

Bleed off the air in high points in 
the secondary system 

Annoying noise in the 
secondary system 

Pump capacity too high 

Reduce the pump capacity by 
choosing a lower output setting on 
the pump, if available 

Temperature “hunting” of 
secondary system 

Settings not correct 

Adjust control parameters or call a 
service technician 

Secondary side flow too low 

Increase the speed of the pump by 
choosing a higher output setting (if 
available) or adjust by opening a 
balancing valve 

Secondary system often 
needs topping up 

The expansion vessel cannot 
handle the changes in volume. 
 

Call service technician to check 
the volume take-up and pressure 
priming of the expansion vessel, or 
possible leakage 

Leakage 

Secondary side temperature 
too high 

District cooling filter clogged 

Contact a service technician 

District cooling water 
temperature too high 

Contact the district energy supplier 

See also the installation instructions. 

 
Warning! 

 
Children must not be left unattended in the area of the district cooling substation. 

 

High pressure water may escape when you open safety valves, drain cocks, filters and air 
bleed valves. Take care. 

To maintain the CE-marking status of the product, any replacement components fitted must 
be identical to those replaced. 
 
Make sure that supplied or after- mounted safety equipment works properly, is set correctly 
and have the right effect, to avoid wrong-tempered water to reach the building. 