Cetetherm Mini Plus CM737
Installation, service and operating instruction
13
7.2
Installing the outdoor temperature sensor
Connect the outdoor temperature sensor to the terminal strip in accordance with the electrical diagram, remove
any resistor.
With a conductor area of 0.6 mm
2
the maximum cable length is 50 metres and maximum 5Ω/conductor. When
the outdoor temperature sensor cable is connected to a terminal strip, the connecting cable must be long
enough for the controller and its mounting plate to be lifted off.
If the outdoor temperature sensor is connected later, for example in a construction period, the current must be
disconnected for a few minutes.
Set parameter 14 according to requested compensation; see
7.4 Configure the control panel after installation
The installation must be connected to a grounded wall socket.
7.3
Starting up and component control of control panel
Note:
The substation must be filled with water before starting the room thermostat, if not the pump can be
damage.
1. Put the electrical cable from the control panel into a wall outlet.
2. Check the heating actuator (knob turns) on and pump function. In start-up mode, the components
manoeuvre by the following schedule:
•
10s actuator clockwise, if not closed at start
•
10s actuator counter clockwise
•
10s actuator clockwise
•
10s pump runs
•
150s actuator closes
After approximately another 4 minutes the room thermostat changes from start up to normal regulation.
3. Press the
MAN
(8) button for a fixed set point (no reduction) of the room temperature.
4. Adjust the room temperature with the increase/decrease buttons on the right (6).
By outdoor compensation this change represents a standard parallel shift of the heat curve, recalculated for
room temperature. For more details see chapter
8.5 Parallel adjustment of heating curve
7.4
Configure the control panel after installation
The room thermostat can be configured in three different ways. All installation parameters can be found in the
parameter list, see
Activation of installer parameters
The control panel is pre-set to Outdoor compensation.
•
Outdoor compensation, require a connected outdoor temperature sensor,
see
7.2 Installing the outdoor temperature sensor
Set parameter 14:rC to 1.
•
Room compensation, require a mounted room thermostat,
see
7.1 Using the control panel as a room thermostat
Set parameter 14:rC to 0.
•
Outdoor and room compensation, require a connected outdoor temperature sensor and a mounted
room thermostat see
7.2 Installing the outdoor temperature sensor
7.1 Using the control panel as a
Set parameter 14:rC to 2.