Cetetherm Mini Plus CM737
Installation, service and operating instruction
17
8.6
Operating mode Auto
8.6.1
The Built-in Heating Program
The built-in heating program has four temperature level changes per day that can be set between 3.00am and
2.50am the following day - allowing the evening temperature to maintain after midnight. Each temperature level
can be set between 5°C and 35°C, and adjusted in 0.5°C increments.
The factory default program for heating is as:
Monday to Friday (Day 1 to 5)
Period
1
2
3
4
Time
6:30
8:00
18:00
22:30
Temperature
21 °C
18 °C
21 °C
16 °C
Saturday & Sunday (Day 6 & 7)
Period
1
2
3
4
Time
6:30
8:00
18:00
22:30
Temperature
21 °C
18 °C
21 °C
16 °C
8.6.2
Reviewing the Heating Program
To review or edit the heating program use the
PROGRAM
or
buttons to navigate between the four
individual programming periods.
Use the
DAY
button to step through each day of the week, so the complete 7-day heating program can be
reviewed or edited.
8.6.3
Temperature Override
During
AUTO
mode, the programmed temperature can be adjusted manually.
The ‘target’ temperature will be
displayed and flash for 5 seconds - during this time the
or
or buttons can be used to modify the set
value.
NOTE:
This temperature override is cancelled at the next programmed temperature change.
8.6.4
Disabling/enabling time periods
Any of the heating period from 2 to 4 can be removed from (or returned to) the heating program profile.
To disable or enable time periods:
1. To disable unwanted periods, go to the desired period (2 to 4) using the
PROGRAM
or
buttons
to navigate, ensure the correct period is highlighted with the flashing square symbol.
Press and hold the
button for at least 2 seconds and the display will indicate the period has been
removed from the program.
2. To enable periods again, follow the same procedure as above, navigating to the already disabled
period. To enable this period again, press and hold the
button for at least 2 seconds.