Cetetherm Mini Plus CM737
Installation, service and operating instruction
43
17.6 Change the outdoor temperature sensor
1. Disconnect the power feed to the substation.
2. Close the heating actuator by turning the knob clockwise to its
closing position.
3. Unscrew the lid by turning it anti-clockwise.
4. Unscrew the cables.
5. Loosen the cable fitting.
6. Install a new outdoor temperature sensor.
7. Connect the power feed to the substation.
8. Check the sensors value on the control panel after 5 min.
Picture 28
17.7 Change the heating actuator
Maintenance and repairs must be carried out by an authorized service technician.
1. Disconnect the power feed to the substation.
2. At the connection box, disconnect the power cable to the
actuator.
3. Unscrew the heating actuator from the valve, the valve closes.
Picture 29
4. Cut off all straps that holds the actuator cable.
5. Make sure that new actuator is closed by turning the knob
clockwise to the closing position. Fasten the actuator, use only
hand power.
6. Replace cable and straps.
7. Connect the power feed to the substation.
8. Check the function of the actuator during start up.
Picture 30