15
3- Filling water flow meter (Ref. OPTMPDETECT)
The flow meter and its accessories has to be installed before the filling electrovalve, as illustrated
bellow :
The left arrow represents the cold water inlet, filling the storage tank.
Install a gate valve before the flow meter.
Flow meter output is one (1) pulse every ten (10) liters.
Flow meter’ s electric wires must be connected to one of the two available C (common) and I3
terminals of the power board CI572P as per the electric wiring diagram shown below:
4- Room flooding sensor option (Ref. INONDMP)
This level sensor must be connected to one of the two available C (common) and I4 terminals of
the power board CI572P as per the electric wiring diagram shown below: