41
Display and default
setting
Setting range
Instructions and remarks
MODBUS ADRESS
10
0-255
Modbus Adress of the controller
Press + or
– to adjust the value.
When done, press on
yellow (rep.4) to
access next line
MODBUS SPEED
9600 bauds
4800 / 9600 /
19200 / 38400 /
57600 / 115200
Modbus communication speed
Press + or
– to adjust the value.
When done, press on
yellow (rep.4) to
access next line
MODBUS PARITY
Aucune
Aucune / Impaire
/ Paire
Modbus words parity
Press + or
– to adjust the value.
When done, press on
yellow (rep.4) to
access next line
MODBUS STOP BIT
1
1 / 2
Modbus stop bit
Press + or
– to adjust the value.
When done, press on
yellow (rep.4) to
access next line
SAVE MODIFICATIONS
At any time, you can interrupt the setting
procedure and save the changes by pressing the
VALIDATION key.
To save your modifications, Press + for YES
and
– for NO.
ANY PARAMETRE MODIFICATION SHOULD
BE VALIDATED THIS WAY
Both controller and connected BMS must have the same
communication parameters (ID, speed, parity and stop bit)