2
SPECIFICATIONS
INSTALLATION REQUIREMENTS
Model VFG600
Gas type
LPG
Operating pressure
2,8kPa
Min Regulator size to comply with SANS 1237
2 kg/hr
Max. gas consumption
0.56 kg/hr
Max. mJ input
31 mJ/hr
Max. kW input
8 kW/h
Gas inlet connection
Ø8mm compression
Ignition
Piezo Spark
Oxygen depletion system ( Pilot )
ODS min 18.5% O2
Coals 14
Pebbles 14
Min Room size without permanent ventilation
92 m³
Your VFG600 Fireplace is designed to
replace old wood and coal fire
grates and to be used in the more conventional fireplaces.
Choosing a site:
This fireplace may be installed in any room in a home except in bedrooms or
bathrooms where the humidity levels are too high. (See page 1)
Avoid areas where there are strong draughts
, which may be generated by
outside doors. It is recommend that the fireplace
should not
be installed
within 500mm of any air vent, as this could affect the working of the ODS.
Clearances to combustible materials:
Combustible materials are defined as wood, fabrics, or other materials likely
to burn when exposed to flame. Any other material which is likely to discolour,
melt, or lose shape when exposed to moderate heat, should fall into the
same category.
Min clearance to the sides
100 mm
Min clearance to the sides for curtains & fabric
500 mm
Min clearance to the ceiling
800 mm
Min clearance to a floor ( including carpet )
100 mm
Min clearance to combustible furniture in front
1000mm
A masonry shelf may be fitted 800mm above the fireplace
but under no
circumstances should any electrical equipment such as plasma screen
TV sets be positioned on the wall above. Any ornaments positioned above
the fireplace must be able to withstand the elevated temperatures and
moisture. No combustible materials whatsoever must be used or placed
above the fireplace.