3.4  Cabling and Cable Glands

 

The temperature conditions at the supply cable entry point are such that 70°C (ordinary PVC) cable can be used.  Equipment 
certified cable glands and sealing plugs must have suitable

 “Geração E”

 approval. When installed the cable gland or sealing 

plug should maintain the IP rating of the enclosure, IP66/67. 
Four entries are provided.  Three entries are fitted with suitably approved blanking plugs, the fourth entry with a transit plug.  
M20  x  1.5  entries  are  standard,  other  sizes  are  available  on  request.  The  standard  entry  configuration  is  with  an  earthed 
metal plate with tapped holes mounted in the body. 

 
3.5    Electrical Connections and Testing

 

If any work is to be done on any luminaire already connected to the electrical system, the luminaire must be isolated from the 
system. The diffuser cover is swung down and removed, if necessary, by swivelling back as far as possible then lifting off. To 
access  the  mains  terminals  loosen  the  four  fixing  screws,  slide  the  reflector/gear  tray  over  the  slots  and  swing  the 
reflector/gear  tray  down.  Luminaires  are supplied  suitable  for  looping  and  through wiring.   Screw  type  or screw-less  “cage 
clamp” terminals are fitted in the range of luminaires.  Mains terminal blocks are marked L N Earth. 
Mains terminal blocks on the emergency luminaires are marked Lc Ls N Earth. 
Switching the voltage on the Ls connection enables the luminaire to be switched on and off without the emergency function 
being activated.  The Ls connection is insulated from L and has a signal function only drawing a very small current. 
The emergency units can be connected as switched, un-switched or non-maintained units. The switching facility is to allow 
the  luminaire  to  be  switched  off  whilst  still  charging  the  battery.    Where  switching  is  required,  the  un-switched  line  (Lc)  is 
connected  to  the  continuous  mains  supply.    A  link  is  fitted  during  assembly  between  Lc  and  switched  line  (Ls);  this  is 
removed for the switch-able mode.  If the link is removed and Ls not supplied, the unit will only operate on emergency. 
The  maximum  amount  of  insulation  allowed  beyond  the  throat  of  the  terminal  is  1mm.  The  normal  method  of  insulation 
testing  is to connect  Live and  Neutral  together and  test between this  point and Earth  to prevent  the  risk  of  damage  to  the 
electronic control gear. However, if this is not possible luminaires can be tested with an insulation tester that complies with 
IEC  364  or  BS  7671  with  a  maximum  output  current  of  1mA  and  output  voltage  of  500V  dc.  (Units  damaged  by  incorrect 
insulation testing can be detected). Before completing the wiring, ensure that all the connections are correctly introduced into 
place before reassembling the luminaire. 

4.0  Emergency Operation 
4.1

    

General description of operation

 

The luminaire will go seamlessly into emergency mode at not less than 60% rated supply voltage and will remain in mains 
mode above 85% of rated supply voltage. 
The charging function is monitored continuously, there is a check for over charging and no charging. In case of a control gear 
error, the indicator will flash quickly on and off. Batteries will fully charge within 24hrs. 
After a complete battery discharge, the unit will switch over to a low discharge current mode.

  

LED display

 

The status is displayed by means of green LED signals. 
The LED will flash slowly, if the batteries are being charged. 
The LED will be steady at full charge. 
The LED will flash quickly if there is a fault or a warning. 
The LED will be off during emergency operation.

4.2    Low Temperature Operation 

At battery temperatures below 10°C charge time can increase. This temperature is equivalent to the luminaire operating at -
5°C with the LEDs on or at +5°C with the LEDs off. 
Under operating conditions where the ambient temperature is below 0°C for long periods the luminaire should be purchased 
with Low Temperature option. This incorporates a heater to maintain the batteries at a sufficient temperature. 

5.0   Servicing and Operation 
S

afe servicing behind the gear tray requires the mains supply to be isolated.

 

5.1   Opening and Closing the Cover 

Insert a screwdriver into one of the slots in the clamping bar with the end of the tool located into the outer flange of the body 
as a fulcrum point, a wide blade screwdriver is recommended. Gently lever the tool away from the diffuser, the clamping bar 
will begin to open. Insert the tool in the other clamping bar slot and gently lever away from the diffuser, the clamping bar will 
open and the cover will be retained by the hinge.  Should difficulty be experienced reinsert the tool in the first slot and repeat 
the procedure. 