E A R T H G R O U N D R O D I N S T A L L A T I O N
To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the
operator MUST NOT be performed until disconnecting the
electrical power and locking-out the power via the operator
power switch. Upon completion of maintenance the area
MUST be cleared and secured, at that time the unit may be
returned to service.
• Disconnect battery and 34 Vdc transformer or solar panel
BEFORE proceeding. Operator MUST be properly grounded
and connected in accordance with local electrical codes.
NOTE:
The operator should be on a separate fused line of
adequate
capacity.
• ALL electrical connections MUST be made by a qualified
individual.
• DO NOT install ANY wiring or attempt to run the operator
without consulting the wiring diagram. We recommend that
you install an optional reversing edge BEFORE proceeding
with the control station installation.
• ALL power wiring should be on a dedicated circuit and well
protected. The location of the power disconnect should be
visible and clearly labeled.
• ALL power and control wiring MUST be run in separate
conduit.
• BEFORE installing power wiring or control stations be sure
to follow ALL specifications and warnings described below.
Failure to do so may result in SEVERE INJURY to persons
and/or damage to operator.
BLA
CK
MOTOR
WHITE
RED
BRAKE
SINGLE OR MASTER ONLY
SECOND ONLY
BR
O
WN
BLUE
LIMITS
GREEN
BLA
CK
MOTOR
WHITE
RED
BRAKE
BR
O
WN
BLUE
LIMITS
GREEN
CENTER
LOOP
+24 V
A
C
INPUT
SAFETY
LOOP
STRIKE
INPUT
B
URGLAR
ALARM
INPUT
GR
OUND
RADIO
+24 V
OL
T
UL SENSOR
LAKE FOREST, CALIFORNIA
www.eliteaccess.com
REV A
MIRA
CLE SURGE PR
O
TECTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
®
Proper grounding gives an electrical charge, such as from an
electrical static discharge or a near lightning strike, a path from
which to dissipate its energy safely into the earth.
Within
3 Feet
Single piece of
12 gauge wire.
Wiring
All power wiring should be on a dedicated circuit and well protected.
NOTE:
Calculated using NEC guidelines. Local codes and conditions must be reviewed for suitability of wire installation.
Use 14 gauge / 300 watt direct burial, landscape lighting wire NOT to exceed 500 ft., use 10 gauge wire up to 1000 ft. for transformer.
To prevent SERIOUS INJURY or DEATH from a moving gate:
DO NOT disconnect the audio alarm or reset button.
To AVOID damaging 34 Vdc plug-in transformer, it MUST be
enclosed in a suitable weatherproof enclosure and provided
with proper weatherproof fixtures.
Check local
codes for
proper
depth.
Without this path, the intense energy generated by lightning could
be directed towards the gate operator. Although nothing can
absorb the tremendous power of a direct lightning strike, proper
grounding can protect the gate operator in most cases.
The earth ground rod must be located within 3 feet from the gate
operator. Use the proper type earth ground rod for your local area.
The ground wire must be a single, whole piece of wire. Never
splice two wires for the ground wire. If you should cut the ground
wire too short, break it, or destroy its integrity, replace it with a
single wire length.
Surge Suppressor
CAUTION
WARNING
WARNING
To AVOID damaging gas, power or other
underground utility lines, contact underground
utility locating companies BEFORE digging.
CAUTION
18