6

TO AVOID SERIOUS PERSONAL INJURY OR DEATH
FROM ELECTROCUTION, DISCONNECT ELECTRIC
POWER BEFORE MANUALLY MOVING LIMIT NUTS.

WARNING

CAUTION

WARNING

WARNING

LIMIT SWITCH ADJUSTMENT

MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE
PROCEEDING WITH ADJUSTMENTS.

SENSING EDGES
All types of sensing edges with an isolated normally
open (N.O.) output are compatible with your operator.
This includes pneumatic and electric edges.  If your
door does not have a bottom sensing edge and you
wish to purchase one, contact the supplier of your
operator.

If not pre-installed by the door manufacturer, mount
the sensing edge on the door according to the
instructions provided with the edge.  The sensing
edge may be electrically connected by either coiled
cord or take-up reel. Refer to the steps below.

Important Notes:

a) Proceed with Limit Switch Adjustments before

making any sensing edge wiring connections to
operator as described below.

b) Electrician must hardwire the junction box to the

operator electrical box in accordance with local
codes.

ENTRAPMENT PROTECTION ACCESSORIES (OPTIONAL)

IT IS STRONGLY RECOMMENDED THAT A
SENSING EDGE OR OTHER ENTRAPMENT
PROTECTION DEVICE BE USED IN
CONJUNCTION WITH THIS OPERATOR.

If other problems persist, call our toll-free number for
assistance - 1-800-528-2806.

1.  To adjust limit nuts depress retaining plate to allow

nut to spin freely.  After adjustment, release plate
and ensure it seats fully in slots of both nuts.

2.  To  increase door travel, spin nut away  from

actuator. To decrease door travel, spin limit nut
toward actuator.  

3.  Adjust open limit nut so that door will stop in open

position with the bottom of the door even with top
of door opening.

4.  Repeat Steps 1 and 2 for close cycle. Adjust close

limit nut so that actuator is engaged as door fully
seats at the floor.

15

Retaining Plate

CLOSE Limit Switch

SAFETY
(Aux. Close) Limit Switch

OPEN Limit Switch

Actuator

Aux. OPEN Limit Switch

WIRING:

For wiring of your sensing device to the operator,
refer to the schematic diagram supplied with your
operator.  See field connection terminals identified
as Sensing Device or Safety Edge.

TAKE-UP REEL: Take-up reel should be installed
12" above the top of the door.

COIL CORD:  Connect operator end of coil cord to
junction box (not supplied) fastened to the wall
approximately halfway up the door opening.

ILLUSTRATED PARTS – ELECTRICAL BOX

Summary of Contents for GH 5HP

Page 1: ...L INTERLOCK 3 10 4 5 4 5 Remove Jumper When Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card...

Page 2: ...al door operation ELECTRICAL TRANSFORMER 3PH 208 230 480 VAC 24VAC OR 3PH 575VAC 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE Standard C2 Wiring Standard operators are shipped from the factory set for C2 wiring which requires momentary contact to open constant pressure to close stop on release Optional B2 Wiring Which requires momentary contact to open close and st...

Page 3: ...uide The GH operator may be mounted on either the right standard or left side of door and in either a vertical standard or horizontal mounting position Refer to the steps below if you require the hand chain and or disconnect chain to be on the opposite side of the operator Or if the operator is being mounted in a horizontal position Hand Chain Right Left Conversion Remove the outer snap ring secur...

Page 4: ...ter link 4 Raise operator to approximate mounting position using suitable lifting apparatus and position chain over operator sprocket 5 Raise or lower operator until the chain is taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mounting bracket 6 Align sprockets and secure see Figure 5 FIGURE 4 FI...

Page 5: ...Actuator Radial Ball Bearing Spacer Shim Washer Shoulder Bolt 3 8 Body x 5 8 Long 1 1 2 2 6 4 09 17987 1 10 17983 12 18052 31 18054 80 10022 82 SH31 10S K75 18324 HAND CHAIN SHAFT KIT ITEM PART DESCRIPTION QTY H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Bevel Gear Bevel Gear Shaft Flanged Bearing Compression Spring Spacer Shim Washer 050 Thk Shim Washer 3 8 I D x 010 Thk Dowel Pin 3 16 Dia x 1 25 Long ...

Page 6: ...ORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR If other problems persist call our toll free number for assistance 1 800 528 2806 1 To adjust limit nuts depress retaining plate to allow nut to spin freely After adjustment release plate and ensure it seats fully in slots of both nuts 2 To increase door tra...

Page 7: ...ange Bearing Bearing Seal 3 8 I D Limit Nut Neoprene Gasket Sprocket 48B18 x 3 8 Bore Washer Shim Screw 8 32 Nut 8 32 Serrated Flange Roll Pin 1 8 DIA x 1 Long E Ring 3 8 Qty 1 2 2 2 2 1 32 4 4 1 2 P N 11 10480 12 10481 12 10483 13 10024 13 10516 15 48B18AXX 80 10026 82 PX08 10T 84 FN 08 86 RP04 100 87 E 038 COMPLETE ELECTRICAL BOX KITS Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Description...

Page 8: ...LE BUT AWAY FROM THE DOOR AND ITS HARDWARE IF CONTROL STATION CANNOT BE INSTALLED WHERE DOOR IS VISIBLE OR IF ANY DEVICE OTHER THAN THE CONTROL STATION IS USED TO ACTIVATE THE DOOR A REVERSING EDGE MUST BE INSTALLED ON THE BOTTOM OF THE DOOR FAILURE TO INSTALL A REVERSING EDGE UNDER THESE CIRCUMSTANCES MAY RESULT IN SERIOUS INJURY OR DEATH TO PERSONS TRAPPED BENEATH THE DOOR W A R N I N G TO PREVE...

Page 9: ...allel with the OPEN button More than one device may be connected in this manner Use 16 gauge wire or larger for all controls DO NOT USE THE CONTROL CIRCUIT TRANSFORMER 24VAC IN THE OPERATOR TO POWER ANY ACCESS CONTROL EQUIPMENT OTHER THAN A STANDARD TYPE RADIO RECEIVER External Interlock Switch The operator has a terminal connection for an external interlock switch This switch must be a normally c...

Page 10: ... the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to ...

Page 11: ... the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to ...

Page 12: ...allel with the OPEN button More than one device may be connected in this manner Use 16 gauge wire or larger for all controls DO NOT USE THE CONTROL CIRCUIT TRANSFORMER 24VAC IN THE OPERATOR TO POWER ANY ACCESS CONTROL EQUIPMENT OTHER THAN A STANDARD TYPE RADIO RECEIVER External Interlock Switch The operator has a terminal connection for an external interlock switch This switch must be a normally c...

Page 13: ...LE BUT AWAY FROM THE DOOR AND ITS HARDWARE IF CONTROL STATION CANNOT BE INSTALLED WHERE DOOR IS VISIBLE OR IF ANY DEVICE OTHER THAN THE CONTROL STATION IS USED TO ACTIVATE THE DOOR A REVERSING EDGE MUST BE INSTALLED ON THE BOTTOM OF THE DOOR FAILURE TO INSTALL A REVERSING EDGE UNDER THESE CIRCUMSTANCES MAY RESULT IN SERIOUS INJURY OR DEATH TO PERSONS TRAPPED BENEATH THE DOOR W A R N I N G TO PREVE...

Page 14: ...ange Bearing Bearing Seal 3 8 I D Limit Nut Neoprene Gasket Sprocket 48B18 x 3 8 Bore Washer Shim Screw 8 32 Nut 8 32 Serrated Flange Roll Pin 1 8 DIA x 1 Long E Ring 3 8 Qty 1 2 2 2 2 1 32 4 4 1 2 P N 11 10480 12 10481 12 10483 13 10024 13 10516 15 48B18AXX 80 10026 82 PX08 10T 84 FN 08 86 RP04 100 87 E 038 COMPLETE ELECTRICAL BOX KITS Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Description...

Page 15: ...ORIES OPTIONAL IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR If other problems persist call our toll free number for assistance 1 800 528 2806 1 To adjust limit nuts depress retaining plate to allow nut to spin freely After adjustment release plate and ensure it seats fully in slots of both nuts 2 To increase door tra...

Page 16: ...Actuator Radial Ball Bearing Spacer Shim Washer Shoulder Bolt 3 8 Body x 5 8 Long 1 1 2 2 6 4 09 17987 1 10 17983 12 18052 31 18054 80 10022 82 SH31 10S K75 18324 HAND CHAIN SHAFT KIT ITEM PART DESCRIPTION QTY H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Bevel Gear Bevel Gear Shaft Flanged Bearing Compression Spring Spacer Shim Washer 050 Thk Shim Washer 3 8 I D x 010 Thk Dowel Pin 3 16 Dia x 1 25 Long ...

Page 17: ...ter link 4 Raise operator to approximate mounting position using suitable lifting apparatus and position chain over operator sprocket 5 Raise or lower operator until the chain is taut not tight Make sure the operator output shaft is parallel to door shaft and sprockets are aligned When in position secure the operator to wall or mounting bracket 6 Align sprockets and secure see Figure 5 FIGURE 4 FI...

Page 18: ...uide The GH operator may be mounted on either the right standard or left side of door and in either a vertical standard or horizontal mounting position Refer to the steps below if you require the hand chain and or disconnect chain to be on the opposite side of the operator Or if the operator is being mounted in a horizontal position Hand Chain Right Left Conversion Remove the outer snap ring secur...

Page 19: ...al door operation ELECTRICAL TRANSFORMER 3PH 208 230 480 VAC 24VAC OR 3PH 575VAC 24VAC CONTROL STATION NEMA 1 three button station OPEN CLOSE STOP WIRING TYPE Standard C2 Wiring Standard operators are shipped from the factory set for C2 wiring which requires momentary contact to open constant pressure to close stop on release Optional B2 Wiring Which requires momentary contact to open close and st...

Page 20: ...L INTERLOCK 3 10 4 5 4 5 Remove Jumper When Interlock is Used ONE 2 OR MORE STANDARD 1 2 3 4 Stop Close Open IMPORTANT NOTES 1 The 3 Button Control Station provided must be connected for operation 2 If a STOP button is not used a jumper must be placed between termianls 3 and 4 3 Auxiliary control equipment may be any normally open two wire device such as pullswitch single button loop detector card...

Reviews: