1
ADDENDUM
FOR CSW AND CSL GATE OPERATORS
AUXILIARY RELAY SWITCHES
AUX RELAY
SETTING
SWITCH
SETTINGS
AUX RELAY 1
AUX RELAY 2
1
2
3
Off (no feature
selected)
OFF OFF OFF
Relay always off. Use this Aux Relay setting to conserve
battery power.
Relay always off. Use this Aux Relay setting to conserve battery power.
Open Limit
Switch
OFF OFF ON
Energizes at open limit. Use with SAMS (Sequenced Access Management
System, jointly with barrier gate)
Energizes when at open limit. Use with SAMS (Sequenced Access
Management System, jointly with barrier gate)
Close Limit
Switch
OFF ON OFF
Energizes when not at close limit. Connect “Gate Close/Secure” indicator
(e.g. light).
Energizes when not at close limit. Connect “Gate Not Closed/Secure”
indicator (e.g. light).
Gate Motion
OFF ON ON
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
indicator (e.g. warning light or sounder).
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
indicator (e.g. warning light or sounder).
Pre-Motion
Delay
ON OFF OFF Energizes 3 seconds before gate motion and remains energized during gate
motion. Connect “Gate In Motion” indicator (e.g. warning light or sounder).
Not used.
Power
ON ON OFF Energizes when AC power or solar power is present. There is approximately
a 10-12 second delay before relay cutoff, after AC shutdown.
Energizes when on battery power. There is approximately a 10-12
second delay before relay cutoff, after AC shutdown.
Tamper
ON OFF ON
Energizes if gate is manually tampered with by being pushed off of close
limit. Connect alert (e.g. light or sounder).
Energizes if gate is manually tampered with by being pushed off of close
limit. Connect alert (e.g. light or sounder).
Cycle Quantity
Feedback*
ON ON ON
The OPEN, CLOSE, and STOP LEDs will blink out the cycle count
See below.
Not used.
AUX RELAY switches
Set the AUX RELAY switches as needed to obtain the desired function:
Com
Single
Button
Control
Station
SBC
3-Button
Control
Station
Com
Open
Close
Stop
AUX Relay 2 N.C.
Com
AUX Relay 2 N.O.
AUX Relay 1 N.C.
Com
AUX Relay 1 N.O.
Exit Loop
Interrupt Loop
Shadow Loop
CYCLE COUNT
* First, note the current Aux Relay switch positions. To
determine the actual cycles that the gate operator has
run (in thousands), set all three Aux Relay switches to
the ON setting for Aux Relay 1. The Expansion Board’s
OPEN, CLOSE, and STOP LEDs will blink out the cycle
count, with OPEN LED blinking 1000’s, CLOSE LED blink
10,000’s, STOP LED blinking 100,000’s, and
simultaneously all three LED’s blink 1,000,000’s (e.g.
Open blinks 3 times, Close blinks 6 times, and Stop
blinks once. Cycle count is 163,000.). Cycle count
displayed is between 1,000 and 9,999,000 cycles.
After servicing, set Aux Relay switches back to their
appropriate positions. Cycle count cannot be reset or
changed. If under 1,000 cycles the Open, Close, and
Stop LEDs will turn on for 10 seconds, then turn off.
The reset switch is located on the front of the operator and serves several functions.
Toggling the reset switch will stop a moving gate during a normal open/close cycle,
like a stop button. The operator does not need to be reset after doing this. The reset
switch will disable the gate in the present position and will energize the solenoid lock
for two minutes and disable the maglock for two minutes.
MANUAL DISCONNECT
Press the reset switch to RESET/DISCONNECT to allow the gate to be opened and
closed manually. To resume normal operation press the reset switch to NORMAL
OPERATION.
RESET/DISCONNECT
NORMAL OPERATION
MODELS CSL24V AND CSL24VH
RESET SWITCH