background image

1

ADDENDUM

FOR CSW AND CSL GATE OPERATORS

AUXILIARY RELAY SWITCHES

AUX RELAY 

SETTING

SWITCH 

SETTINGS

AUX RELAY 1

AUX RELAY 2

1

2

3

Off (no feature 

selected)

OFF OFF OFF

Relay always off. Use this Aux Relay setting to conserve 

battery power.

Relay always off. Use this Aux Relay setting to conserve battery power.

Open Limit 

Switch

OFF OFF ON

Energizes at open limit. Use with SAMS (Sequenced Access Management 

System, jointly with barrier gate)

Energizes when at open limit. Use with SAMS (Sequenced Access 

Management System, jointly with barrier gate)

Close Limit 

Switch

OFF ON OFF

Energizes when not at close limit. Connect “Gate Close/Secure” indicator 

(e.g. light).

Energizes when not at close limit. Connect “Gate Not Closed/Secure” 

indicator (e.g. light).

Gate Motion

OFF ON ON

Energizes when motor is on (gate in motion). Connect “Gate In Motion” 

indicator (e.g. warning light or sounder).

Energizes when motor is on (gate in motion). Connect “Gate In Motion” 

indicator (e.g. warning light or sounder).

Pre-Motion 

Delay

ON OFF OFF Energizes 3 seconds before gate motion and remains energized during gate 

motion. Connect “Gate In Motion” indicator (e.g. warning light or sounder).

Not used.

Power

ON ON OFF Energizes when AC power or solar power is present. There is approximately 

a 10-12 second delay before relay cutoff, after AC shutdown. 

Energizes when on battery power. There is approximately a 10-12 

second delay before relay cutoff, after AC shutdown.

Tamper

ON OFF ON

Energizes if gate is manually tampered with by being pushed off of close 

limit. Connect alert (e.g. light or sounder).

Energizes if gate is manually tampered with by being pushed off of close 

limit. Connect alert (e.g. light or sounder).

Cycle Quantity 

Feedback*

ON ON ON

The OPEN, CLOSE, and STOP LEDs will blink out the cycle count 

See below.

Not used.

AUX RELAY switches

Set the AUX RELAY switches as needed to obtain the desired function:

Com

Single 

Button 

Control 

Station

SBC

3-Button 

Control 

Station

Com

Open

Close

Stop

AUX Relay 2 N.C.

Com

AUX Relay 2 N.O.

AUX Relay 1 N.C.

Com

AUX Relay 1 N.O.

Exit Loop

Interrupt Loop

Shadow Loop

CYCLE COUNT

*  First, note the current Aux Relay switch positions. To 

determine the actual cycles that the gate operator has 

run (in thousands), set all three Aux Relay switches to 

the ON setting for Aux Relay 1. The Expansion Board’s 

OPEN, CLOSE, and STOP LEDs will blink out the cycle 

count, with OPEN LED blinking 1000’s, CLOSE LED blink 

10,000’s, STOP LED blinking 100,000’s, and 

simultaneously all three LED’s blink 1,000,000’s (e.g. 

Open blinks 3 times, Close blinks 6 times, and Stop 

blinks once. Cycle count is 163,000.). Cycle count 

displayed is between 1,000 and 9,999,000 cycles. 

After servicing, set Aux Relay switches back to their 

appropriate positions. Cycle count cannot be reset or 

changed. If under 1,000 cycles the Open, Close, and 

Stop LEDs will turn on for 10 seconds, then turn off.

The reset switch is located on the front of the operator and serves several functions.
Toggling the reset switch will stop a moving gate during a normal open/close cycle, 

like a stop button. The operator does not need to be reset after doing this. The reset 

switch will disable the gate in the present position and will energize the solenoid lock 

for two minutes and disable the maglock for two minutes.

MANUAL DISCONNECT

Press the reset switch to RESET/DISCONNECT to allow the gate to be opened and 

closed manually. To resume normal operation press the reset switch to NORMAL 

OPERATION.

RESET/DISCONNECT

NORMAL OPERATION

MODELS CSL24V AND CSL24VH

RESET SWITCH

Reviews: