11
INPUT COMMANDS CONNECTIONS
(Use common and normally open contacts from devices
connected to these inputs)
JP2 Input
This input will stop the gate and activate the siren.
This input is for connection to wired contact edge sensors at
pinch points and photo beams that run along either side the gate
panel when in open position (if dead panel is present one beam
should run along it).
Input Commands - J5 Connector Block at top of Control Board
Control wire connections at low voltage terminal strip will be at
the top of the electronic control board. Make connections to the
appropriate points for the desired operation. Wires should be UL
approved 600 volt rated and at least 18 awg. All external control
devices must have normally open dry contacts.
DO NOT
CONNECT ANY DEVICE WHICH WOULD DELIVER ANY VOLTAGE
OF ANY KIND TO THESE TERMINALS.
Terminals 9, 10, 11, 12 are the commons (0 Vdc) used to activate
the following inputs.
Terminals 1, 2, 3 Open -
These inputs will trigger gate open
when pulsed or hold gate open with maintained contact. When
released gate will close if closing timer is on or if close input is
given.
Terminal 4, Auxiliary Open
- This is the wired line of sight,
intended manual reset input. Use this input to reset the unit
after a 2nd sequential obstruction is sensed and gate is locked
with siren running. This input normally functions as listed
below.
Acts same as 1, 2, 3 above with S2-6 off. With S2-6 ON this
will operate as a pulse-open, pulse-close.
NOTE:
Pulse to close will only work when gate is at full open
position.
SIREN will run for 5 minutes after
2nd sequential obstruction
,
then turns itself off, however operator will require a reset signal
to J5 #4 to re-activate gate. In addition, cycling the ac power
will also reset unit.
Terminal 5, Safety -
Safety edge(s) and safety loop input. This
function will make the gate reverse and go back to the open
position if it was closing. Input is for all NORMALLY OPEN
contact safety devices. This input is disabled when gate is in the
full closed position. Use with vehicle loops, photo beams and
sensors.
Terminal 6, Close -
ANTI-TAIL GATE close input. When using a
vehicle detector, you must use the presence contacts (N.O. and
C.) This input will QUICK close gate after input is applied and then
removed. It will stop the open cycle and reverse gate to close.
(Example: Car crosses over close loop before gate reaches full
open position – gate will reverse and close).
NOTE:
The close input also acts as a safety-stop in that if gate is
closing and a tail-gater is sensed at the close input, the gate WILL
STOP its closing motion and not continue to close until the close
input is removed or gate is re-opened.
Terminal 7, Back-Away (For Barrier Arm Gate Only) -
This input
is recommended for use with our Mega Arm barrier gates. For
your Mega Slide X, please use terminals 1, 2 or 3 for your free
exit loop input.
Terminal 8, Shadow Loop -
This input operates as a hold open
only when gate is a full open position.
Terminals 9, 10, 11, 12 Common -
These inputs used for
common (0 Vdc) to above listed functions.
NOTE:
J5 inputs 1-8 are tied to LED indicators to assist in trouble
shooting.
3-Button Control Station -
Not already in place. See diagram
below.
J5 Input #6
J5 Input #1
J5 Commons #9-12
Stop
Close
Open
JP2 Connector
(
NOTE:
Siren will sound
when stop button is
depressed)