11
FULL SPEED RUN TIMER - SWITCH PACK S1 (1-5)
To change the FAST SPEED run timer, set the dip switches to add
up to the number of feet, minus one foot, for the total feet of
travel across roadway.
Example: If road is 15' wide, then set dip switches to add up to
14 seconds (dips 2, 3, 4 are on) which is 2 s 4 seconds
+ 8 seconds = 14 seconds. You must set FULL SPEED to end
before the end of travel and allow the gate to go to the slow
speed before stopping.
MODE SELECTIONS - SWITCH PACK S1 (6-8)
SWITCH 6:
FAIL SECURE MODE, (VER 6.351 or higher) with
AC power off, in continuous battery back up mode (S2 #8 off)
gate will not auto open if batteries get low. If batteries are low,
gate will stay open after an open command is given.
SWITCH 7:
No longer used as of August 16, 2003. To be
redefined.
SWITCH 8:
Not used at this time (ver 6.34 or higher only).
CLOSE TIMER - SWITCH PACK S2 (1-5)
On the MEGA SLIDE UL the switches 1-5 on S2 are for the
closing timer delay. If S2-7 is on, the gate will auto close by
timer. Default is S2-3 “on” to provide a 4 second delay if
activated.
MODE SELECTIONS - SWITCH PACK S2 (6-8)
SWITCH 6:
Sets auxiliary open input terminal #4 at J5 to be
pulse open
--
pulse close
(example: residential applications).
SWITCH 7 - AUTO CLOSE TIMER:
Default is
OFF
. When on,
use S2 1-5 to set close time delay.
When close timer is selected,
YOU
must install vehicle and
pedestrian detection devices. It is strongly recommended that
photoelectric beams (eyes) be installed on
BOTH
sides of the
slide gate to reduce the possibility of injury to persons that
may attempt to walk through gate opening. Along with the
beams, it is strongly recommended that pressure sensing
edges be installed on the leading edge of the gate panel, and
any area that presents a
PINCH POINT
or risk of
ENTRAPMENT
.
SWITCH 8 - AUTO OPEN ON POWER FAILURE:
When switch
number 8 is in the
ON
position, the operator will automatically
open the gate approximately 15 seconds after the loss of
power. Once power is restored, the operator will resume
normal operation.
Seconds - -
1 - - 2 - - 4 - - 8 - -
S1
Shows
Default
Settings
Fast Run Timer 1-5
Mode Selection 6-8
1 2 3 4 5 6 7 8
ON
Mode Selection 6-8
Seconds - -
16
1 - - 2 - - 4 - - 8 - - 16
S2
Shows
Default
Settings
Close Timer 1-5
1
ON
2 3 4 5 6 7 8
T I M E R S A N D M O D E S E L E C T I O N S S 1 & S 2