FULL SPEED RUN TIMER - SWITCH PACK S1 (1-5)

To change the FAST SPEED run timer, set the dip switches to add
up to the number of feet, minus one foot, for the total feet of
travel across roadway.

Example: If road is 15' wide, then set dip switches to add up to
14 seconds (dips 2, 3, 4 are on) which is 2 s 4 seconds
+ 8 seconds = 14 seconds. You must set FULL SPEED to end
before the end of travel and allow the gate to go to the slow
speed before stopping.

MODE SELECTIONS - SWITCH PACK S1 (6-8)

SWITCH 6:

FAIL SECURE MODE, (VER 6.351 or higher) with

AC power off, in continuous battery back up mode (S2 #8 off)
gate will not auto open if batteries get low. If batteries are low,
gate will stay open after an open command is given.

SWITCH 7:

No longer used as of August 16, 2003. To be

redefined.

SWITCH 8:

Not used at this time (ver 6.34 or higher only).

CLOSE TIMER - SWITCH PACK S2 (1-5) 

On the MEGA SLIDE UL the switches 1-5 on S2 are for the
closing timer delay. If S2-7 is on, the gate will auto close by
timer. Default is S2-3 “on” to provide a 4 second delay if
activated.

MODE SELECTIONS - SWITCH PACK S2 (6-8)

SWITCH 6:

Sets auxiliary open input terminal #4 at J5 to be

pulse open

--

pulse close

(example: residential applications).

SWITCH 7 - AUTO CLOSE TIMER:

Default is 

OFF

. When on,

use S2 1-5 to set close time delay.

When close timer is selected, 

YOU

must install vehicle and

pedestrian detection devices. It is strongly recommended that
photoelectric beams (eyes) be installed on 

BOTH

sides of the

slide gate to reduce the possibility of injury to persons that
may attempt to walk through gate opening. Along with the
beams, it is strongly recommended that pressure sensing
edges be installed on the leading edge of the gate panel, and
any area that presents a 

PINCH POINT

or risk of

ENTRAPMENT

.

SWITCH 8 - AUTO OPEN ON POWER FAILURE:

When switch

number 8 is in the 

ON

position, the operator will automatically

open the gate approximately 15 seconds after the loss of
power. Once power is restored, the operator will resume
normal operation.

Seconds - -

1 - - 2 - - 4 - - 8 - -

 S1

Shows
Default
Settings

Fast Run Timer 1-5

Mode Selection 6-8 

1 2 3 4 5 6 7 8

ON

Mode Selection 6-8 

Seconds - -

16

1 - - 2 - - 4 - - 8 - - 16

 S2

Shows
Default
Settings

Close Timer 1-5

1

ON

2 3 4 5 6 7 8

T I M E R S   A N D   M O D E   S E L E C T I O N S   S 1   &   S 2

Summary of Contents for LIFTMASTER PROFESSIONAL MSLDCBB

Page 1: ...unit must only be installed by an experienced technician Disconnect AC power and batteries before servicing IMPORTANT Read and understand Warranty Page first Batteries not included MUST be connected f...

Page 2: ...t Locations 16 MEGA SLIDE UL PARTS LIST Part Numbers and Descriptions 17 Parts Shipped 17 OPERATOR NOTES 18 WARRANTY 19 REPAIR PARTS AND SERVICE 20 TA B L E O F C O N T E N T S IMPORTANT SAFETY INSTRU...

Page 3: ...is class operator is approved for the application of the operator 1 2 3 or 4 required ______ A sphere with a 2 1 4 diameter cannot be pushed through the gate or fixed panel ______ A safety screen mesh...

Page 4: ...erator must be in the line of sight and must be an intended reset Access control devices of any kind that required intended on purpose activation may be used for this reset Devices that will cause an...

Page 5: ...e secondary stop photo beam should be installed along the gate s path that is covered when open Photo beams are to be installed according to their manufacturer s instructions and are to be placed in a...

Page 6: ...ds installed covering all cantilever wheels required All controls located far out of reach of gate fixed panel and operator required This class operator is approved for the application of the operator...

Page 7: ...y to persons use photo electric eyes on both sides of gate and pressure sensing edges at all pinch points and at the front leading edge of the gate Safety loops vehicle detectors should be installed i...

Page 8: ...helf maybe installed after all conduits are cut to proper height and all wiring has been properly routed NOTE Do not attempt to hook up the 120VAC mains if wires are LIVE or HOT Be sure power is off C...

Page 9: ...is input to reset the unit after a 2nd sequential obstruction is sensed and gate is locked with siren running This input normally functions as listed below Acts same as 1 2 3 above with S2 6 off With...

Page 10: ...R any input at J5 with control detectors receivers keypads timers etc wires to it must also be run to the same terminals of the second Along with these control wires both operators MUST share a common...

Page 11: ...delay if activated MODE SELECTIONS SWITCH PACK S2 6 8 SWITCH 6 Sets auxiliary open input terminal 4 at J5 to be pulse open pulse close example residential applications SWITCH 7 AUTO CLOSE TIMER Defaul...

Page 12: ...vel as possible but still ensuring that it will slow down just before reaching the closed position INSTANT REVERSE DEVICE IRD The instant reverse device is an internal circuit that continuously monito...

Page 13: ...can be used with up to 15 rolling code remotes or passwords in HIGH security mode Alternately it can be used with up to 31 of any type remote in NORMAL security mode including any combination of roll...

Page 14: ...the right side of the gate operator frame Once turned off motor will not run and gate can be pushed by hand T R O U B L E S H O O T I N G Flip switch up for normal operation Flip switch down to diseng...

Page 15: ...DEVICE Gate will open when activated by an access control device When timer expires if used gate will close Figure 2 Terminal 5 is safety input Terminals 1 2 and 3 are open inputs DUAL DIRECTION AS E...

Page 16: ...AC XFMR MOTOR RED YEL YEL BLU ORG 24VDC REQULATED F4 F3 1 AMP DC F1 H BEAT BATTERY LOW AC POWER C O N T R O L B O A R D L AY O U T COMPONENT LOCATIONS Accessory power is 24VDC regulated rated at 500...

Page 17: ...BER DESCRIPTION 12 MS014 Siren 100 db 13 MS015 Transformer 110 220 VAC 24VAC 14 MS016 Duplex Outlet MS017 Bolt and Nut 4 Reducer 15 MS018 Idler Pulley Bolt Washer and Nut 16 MS019 120 VAC On Off Switc...

Page 18: ...18 OPERATOR NOTES...

Page 19: ...erating freely or not on level ground The warranty set forth above is entirely exclusive and no other warranty whether written or oral is expressed or implied LiftMaster inc specifically disclaims any...

Page 20: ...andard Time 6 00 A M TO 7 00 P M Monday through Friday 8 00 A M TO 4 30 P M Saturday www liftmaster com WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION PART NUMBER PART NAME MODEL NUM...

Reviews: