background image

26

OPERATOR FAILS TO RUN

CONTACTOR CHATTERS
WHEN OPERATOR BEGINS
TO MOVE

OPERATOR RUNS SLOW
AND/OR TRIPS THE
INTERNAL OVERLOAD

MASTER OR SECOND
OPERATOR IS NOT
FUNCTIONING PROPERLY

1) Improper wired stop control

2)   Fault in the operator 

check the yellow 

diagnostic LED at the top right of the 
control board next to the programming dip 
switches.

3)  An accessory is active or malfunctioning 

check the red input status LEDs, D11-D31

4)  Improper J4 connector wiring 

(master/second)

5)  Low or no high voltage power

6)  Low or no low voltage power

7)   No LEDs illuminated on the 

control board

T R O U B L E S H O O T I N G

  Check the green LED (D17) on control board. If the green LED is off, check to 

make sure a stop control has been installed across terminals TB1-3 and TB1-5 
of the terminal strip.

  If the yellow LED blinks six times, there is a master/second unit 

communication failure. If operator is a single unit, make sure there is a jumper 
across terminals TB1-11 and TB1-12. If operator is in a dual gate 
configuration, make sure that the communication wiring between the two units 
is undamaged and complete.

➤ 

 If the yellow light is solid, the board needs to learn the motor. Follow the 
directions on page 22.

➤ 

 If any red LEDs are on, check the corresponding input. An installed accessory 
may be wired incorrectly or malfunctioning. Remove the accessory and test 
the operator.

➤ 

 If the open or interrupt (safety) loop LED is on, make sure factory plug-in loop 
detectors are working properly and appropriate loops are installed on the loop 
input terminals.

➤ 

 Stand-Alone Operators: Make sure there is a jumper installed across the J4 
connector.

➤ 

 Master/Second Operation: Make sure that the master/second wiring is installed 
correctly and is intact (not damaged).

➤ 

 Verify power supply to operator. It should be within 5% of the operator’s 
rating when running. Make sure that the proper wire gauge was used for the 
distance between breaker and operator by consulting the wiring specifications 
section on page 8 of this manual.

➤ 

 Measure the voltage at terminals R1 and R2 in the operator. This voltage 
should be within 5% of 24Vac. If the high voltage power is good and the low 
voltage power is bad, check to make sure the circuit fuse is not tripped and 
that the correct primary tap is used on the transformer. If fuse and tap are 
correct, replace the transformer.

➤ 

 If both primary and secondary power is good, check to make sure that the J2 
connector is making good contact with the pins on the control board. If all is 
good, replace the control board.

1)  Transformer’s secondary is overloaded

2)  Low primary (high voltage) power

➤ 

  Remove all accessory devices and test the operator. If the contactor stops 
chattering, find an alternate power source for some of the devices.

➤  

Verify power supply to operator. It should be within 5% of the operator’s 
rating when running. Make sure that the proper wire gauge was used for the 
distance between breaker and operator by consulting the wiring specifications 
section on page 8 of this manual.

1)  Low primary (high voltage) power

2)  Problem in the motor

3)  Problem in the contactor

4)  Problem in the brake system

➤  

Verify power supply to operator as well as the meter base or sub panel. Make 
sure there is not a major change in voltage. The voltage at the operator should 
be within 5% of the operator’s rating when running.

➤  

Check the number of amps currently being drawn from the panel. Make sure 
that the total power being drawn does not exceed the panel’s rating.

➤ 

   Make sure that the proper wire gauge was used for the distance between 
breaker and operator by consulting the wiring specifications section on page 8 
of this manual.

➤ 

 Perform a visual inspection of the motor. Examine the motor’s labels for any 
distortion or signs of overheating. Replace the motor if it is humming, grinding 
or making excessive noise. 

NOTE:

 Repeated motor problems indicate poor 

primary power.

➤  

Examine the contactor for sparking, smoke or burn marks. Remove the wires 
from one side of the contactor, then measure the contact points for high 
resistance (above 1 ohm). Replace the contactor.

➤ 

 Make sure that the brake is disengaging when the contactor pulls in and 
engaging when the contactor releases. Replace solenoid.

FAULT POSSIBLE 

CAUSE 

FIX

1)  Failure to cycle power after setup

2)   Communication wiring may be damaged or 

improperly wired for dual gate operation

3)  Master or second unit is not programmed 

correctly

4)  Master/second connection not properly 

grounded

➤ 

 The power to each unit must be cycled in order to initiate proper master/
second communication if the operators were previously in stand-alone mode.

➤ 

 Make sure that the communication wire that is used is twisted pair and not 
run in the same conduit with any power wiring. Failure to do so will result in 
interference across the master/second communication line.

➤ 

 Review program settings page 19 and check both the master and second for 
proper programming.

➤ 

 Review wiring detail for master/second systems on page 20.

Summary of Contents for LiftMaster Professional SL575

Page 1: ..._____________ located on electrical box cover Installation Date__________________ 2 YEAR WARRANTY MODEL SL575 IS FOR VEHICULAR PASSAGE GATES ONLY AND IS NOT INTENDED FOR PEDESTRIAN PASSAGE GATE USE MO...

Page 2: ...y instructions CARTON INVENTORY Before beginning your installation check that all components were supplied and received undamaged Refer to list below for factory supplied parts HARDWARE KIT K77 34846...

Page 3: ...30 ft 9 1 m 1 HP Motor Maximum Cycle Rate 18 cycles per hour At Maximum Gate Weight Maximum Gate Speed 10 sec 25 4 cm sec Maximum Gate Weight 1800 lbs 816 5 kg Maximum Cantilever Gate Width 32 ft 9 8...

Page 4: ...protection Type C Inherent adjustable clutch or pressure relief valve Type D Connections provided for a control requiring continuous pressure to operate the operator open and close Type E Built in aud...

Page 5: ...nded for user activation must be located at least six feet 6 away from any moving part of the gate and where the user is prevented from reaching over under around or through the gate to operate the co...

Page 6: ...y Loop 4 1 2 m Typical Photo eye for open cycle Photo eye for close cycle 8 2 4 m Open Edge Telephone Entry System 1 1 2 37 mm 1 4 6 mm or larger for loop wire width depending on loop wire size STREET...

Page 7: ...both inside and outside of a vehicular horizontal slide gate Non contact sensors such as photo eyes MUST protect during both open and close gate cycles Injuries occur when people put their hands and a...

Page 8: ...control station installation ALL power wiring should be on a dedicated circuit and well protected The location of the power disconnect should be visible and clearly labeled ALL power and control wirin...

Page 9: ...2 2 Locate electrical conduit as required prior to pouring concrete 3 Pour concrete pad 4 Secure operator Figure 3 to the concrete pad using four 1 2 concrete anchors not provided Figure 1 Figure 2 Fi...

Page 10: ...d pipe Posts should be parallel and square to the gate Figure 2 2 Locate electrical conduit as required prior to pouring concrete 3 Secure operator Figure 3 to posts using four 3 7 6 cm U bolts and ha...

Page 11: ...ck for every 10 3 m of chain length Do not overtighten chain NOTE ABOUT SOME TYPES OF CANTILEVER GATES With some cantilever gates over 20 6 m long you may need to add a brace along the length of the g...

Page 12: ...ire gauges Secure all electrical power connections inside the disconnect switch electrical box Refer to electrical wiring diagrams on pages 30 and 32 115VOLT 1 PH USE COPPER CONDUCTO R ONLY 115VOLT 1...

Page 13: ...entered over the magnet wheel Adjust with horizontal screws 2 The sensor must be level 3 The sensor air gap should be adjusted to 010 015 of an inch The thickness of a business card may be used to gau...

Page 14: ...input photo eye is cleared the gate continues to open Activating this input when the gate is closing will have no effect Terminals 10 5 Obstruction While Closing Edge Photo Eye Input Edge Input See P...

Page 15: ...put functions to reverse the gate to the open limit when activated during the close cycle The entrapment is not cleared at the limit and the Timer to Close will be disabled The Timer to Close may be e...

Page 16: ...This switch enables the Maglock feature On an open command there will be a half second delay after the maglock relay is released before the motor starts WARNING ENABLE This switch enables the gate in...

Page 17: ...hroughout the manual Installation device instructions Always follow the instructions provided by the manufacturer when installing and adjusting any control device If these instructions are contrary to...

Page 18: ...erate at the NORMAL mode Figure 1 When changing from NORMAL to HIGH security mode any previous remote control codes must be erased Repeat Steps 2 and 3 in the Programming Section see page 19 to reprog...

Page 19: ...ERASE ALL REMOTE CONTROL CODES Press and hold the learn button on the receiver panel until the indicator light turns off about 6 seconds All remote codes are now erased Then follow the steps above to...

Page 20: ...additional surge protection MASTER SECOND SYSTEMS Dual Gate Communications The control board is capable of running the operator in a master or second mode depending on S4 switch setting Before initia...

Page 21: ...h ground rod must be located within 3 feet from the gate operator Use the proper type earth ground rod for your local area The ground wire must be a single whole piece of wire Never splice two wires f...

Page 22: ...le or pair of slide swing gate operator The design of this gate system balances the demands of speed during high traffic periods with security during low traffic periods Barrier gates typically have t...

Page 23: ...perator Failure to adjust and retest the gate operator properly can increase the risk of INJURY or DEATH 5 Use the emergency release ONLY when the gate is not moving 6 KEEP GATES PROPERLY MAINTAINED R...

Page 24: ...LEARN FUNCTION FORCE PROFILE This function is preprogrammed at factory If either board or motor is replaced the control board will need to be reprogrammed to LEARN the specific motor RPM profile of yo...

Page 25: ...n when Stop switch is not activated D19 Soft Open On when Open switch is activated D21 Hard Open On when Open switch is activated D24 Interrupt Safety Loop On when Interrupt Safety Loop activated D29...

Page 26: ...good check to make sure that the J2 connector is making good contact with the pins on the control board If all is good replace the control board 1 Transformer s secondary is overloaded 2 Low primary h...

Page 27: ...it is adjusted correctly but continues to fail 1 Operator s manual release is not aligned 2 Clutch is not adjusted properly 3 V Belt Slippage Make sure that the unit s manual release is not engaged Th...

Page 28: ...adout is in degrees Celsius White Black L1 L2 Green Ground 1 T ck la B N ack l B ON OFF On Off Switch White Black 1 PHASE 115 VOLT POWER IN Line voltage to operator controls H E A T E R W I R I N G D...

Page 29: ...VAC COMMON DC GND LOCK 1 LOCK 1 ALARM 1 ALARM 1 RADIO SHADOW VDC COM CLOSE STOP COM SOFT OPEN HARD OPEN INTERRUPT SAFETY OPEN CLOSE MASTER SECOND MAGLOCK 24 VAC INTERRUPT LOOP SAFETY EXIT LOOP FIELD...

Page 30: ...A CONTACTOR B A1 4 A1 ORANGE PURPLE OR P 1 2 L S A NC C L S B NC C YEL BLK Y BK GY TB2 BL Y PU GY BL Y PU 1 3 8 5 4 2 OL BK BK BK BK BL BK BL BK 115V BRAKE SOLENOID 115V CONNECTION 230V BRAKE SOLENOID...

Page 31: ...IO 3 PHASE POWER IN ON OFF SWITCH GROUND SAFETY ALARM 100 db NOTES 1 Transformer primary voltage is the same as the operator line voltage Secondary 24V 60VA 2 Wire color 208V red 230V orange 460V purp...

Page 32: ...R4 TB2 AB TB2 CD FREE EXIT LOOP HARNESS 10 PIN TB1 8 TB1 3 TB2 AB TB2 CD INTERRUPT LOOP HARNESS 10 PIN 4 6 7 8 9 10 BK BK PU 7 8 9 4 5 6 460V CONNECTION 230V BRAKE SOLENOID 1 3 2 BL BK BL BK BK BK PU...

Page 33: ...MODEL DESCRIPTION G65MG0204 Miller MG020 2 wire electric edge for gates Sensitized on three sides Requires mounting channel 4 1 2 m long 24V ac dc G65MG0205 Miller MG020 2 wire electric edge for gates...

Page 34: ...h shaft kit Complete with Clutch shaft sprockets e ring compression spring pulley washer bearings retaining ring disconnect splined hub and roll pin NOT SHOWN 19 48047M Roller Chain Sprocket Reduction...

Page 35: ...35 35 5 6 10 K4 K75 34842 1 2 K1 71 B120 71 B208 71 B240 71 B575 K3 K75 34828 K2 K75 34824 K3 K75 34828 3 7 9 8 4 K6 K75 19977 K8 K72 34845 K7 K72 34844 K5 K29 32410 I L L U S T R A T E D P A R T S...

Page 36: ...75 75 21 SL575 75 81 SL575 100 21 SL575 100 81 25 2010 Overload 10 AMP SL575 50 11 25 2015 Overload 15 AMP SL575 100 11 25 4002 SK Overload 1 8 to 2 6 AMP SL575 100 53 NOT SHOWN K74 18379 RPM Sensor H...

Page 37: ...37 N O T E S...

Page 38: ...38 N O T E S...

Page 39: ...39 N O T E S...

Page 40: ...with new or factory rebuilt parts at Seller s sole option ALL IMPLIED WARRANTIES FOR THE PRODUCT INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PU...

Reviews: