background image

27

FAULT POSSIBLE 

CAUSE 

FIX

MASTER OR SECOND
OPERATOR IS NOT
FUNCTIONING PROPERLY

OPERATOR RUNS IN
WRONG DIRECTION

OPERATOR RUNS BUT
THEN STOPS AND
REVERSES DIRECTION

MOTOR RUNS BUT GATE
DOES NOT MOVE;
OPERATOR STOPS AND
ALARMS

OPERATOR OPENS
IMMEDIATELY UPON
POWER UP AND DOES NOT
CLOSE

OPERATOR HAS TROUBLE
LEARNING THE MOTOR

PROGRAMMING CHANGES
DO NOT EFFECT THE GATE

GATE EDGE PAUSES GATE
WHEN STRUCK DURING
OPENING

GATE DOES NOT ACTIVATE
TIMER TO CLOSE AFTER
THE CLOSE PHOTO EYE IS
BROKEN

1)  Failure to cycle power after setup

2)   Communication wiring may be 

damaged or improperly wired for dual 
gate operation

3)  Master or second unit is not 

programmed correctly

T R O U B L E S H O O T I N G

➤ 

 The power to each unit must be cycled in order to initiate proper 
master/second communication if the operators were previously in 
stand-alone mode.

➤ 

 Make sure that the communication wire that is used is twisted pair 
and not run in the same conduit with any power wiring. Failure to do 
so will result in interference across the master/second 
communication line.

➤ 

 Review program settings page 20 and check both the master and 
second for proper programming.

1)  Operator’s main power is out of phase 

(three phases only)

➤ 

 Turn off the unit’s main power at the breaker and swap any two 
power leads at the operator’s main power switch. Apply power and 
retest the operator. See important note on page 12.

1)  Entrapment (force pot) incorrectly set

2)   Gate is binding or not running 

smoothly

3)  Clutch is not adjusted properly

4)  Brake is not functioning properly

5)  Observe red LEDs D29 and D31

6)  RPM (Hall Effect) Sensor

is not aligned

➤ 

 This pot must be set so that the gate will run smoothly normally and 
reverse when encountering an obstruction.

➤ 

 Disengage the manual release and roll gate open and close by hand at 
normal operating speed. Make sure that the gate runs smoothly and 
does not bind. If the gate is hard to move or binds, repair the gate.

➤ 

 Adjust the clutch so that the operator can move the gate throughout 
its travel without slipping but will slip when the gate hits an 
obstruction.

➤ 

 Make sure that the brake operates correctly. The brake should 
disengage when the contactor activates and engage when the 
contactor releases.

➤  

Both LEDs will indicate the activation of entrapment protection 
devices on terminals TB1-9 and TB1-10 on the control board. 
Remove the devices and retest. If the operator now runs without fault, 
check those accessories as well as their wiring.

➤  

Make sure that the sensor is adjusted so that it is centered over the 
limit shaft’s magnet and is 10-15 thousandths of and inch (business 
card thickness) from the magnet.

➤ 

 Replace the sensor if it is adjusted correctly but continues to fail.

1)  Clutch is not adjusted properly

2)  Operator’s manual release is not 

aligned

➤ 

 Adjust the clutch so that the operator can move the gate throughout 
its travel without slipping but will slip when the gate hits an 
obstruction.

➤ 

 Make sure that the manual release is not engaged. The operator’s 
manual release, when engaged, will set off the entrapment if the gate 
is given a command to move.

1)  Active or malfunctioning accessory 

check the red input status LEDs,
D11-D13

➤ 

 If any red LEDs are on, check the corresponding input. An installed 
accessory may be wired incorrectly or malfunctioning. Remove the 
accessory and test the operator.

➤ 

 If the soft open or interrupt (safety) loop LED is on, make sure 
factory plug-in loop detectors are working properly and appropriate 
loops are installed on the loop input terminals.

1)  Operator’s manual release is engaged

➤ 

 Make sure the manual release is not engaged. The operator’s manual 
release, when engaged, will not allow the entrapment sensor to 
provide feedback to the control board when the operator is moving.

1)  Check the save switch on switch S1-1

➤ 

 If the switch S1-1 is in the on position, any subsequent programming 
changes will not affect the gate. To make programming changes, 
switch S1-1 off, make desired changes, and then switch S1-1 on.

1)  Open obstruction input is 

programmed incorrectly

➤ 

 The open obstruction input has been programmed to function with 
photo eyes, not gate edges. Refer to page 15 and reprogram the 
obstruction inputs for correct operation.

1)  Close obstruction input is 

programmed incorrectly

➤ 

 The close obstruction input has been programmed to function with 
gate edges, not photo eyes. Refer to page 15 and reprogram the 
obstruction inputs to match the accessories that are installed on 
operator.

Summary of Contents for LiftMaster Professional SL585

Page 1: ...ox cover Installation Date__________________ 2 YEAR WARRANTY MODELS SL585 AND SL595 ARE FOR VEHICULAR PASSAGE GATES ONLY AND ARE NOT INTENDED FOR PEDESTRIAN PASSAGE GATE USE MODEL SL585 HEAVY DUTY SLI...

Page 2: ...stall Vent Plug 14 UL325 Entrapment Protection 14 15 Control Board Illustration 15 Program Settings 16 Control Connection Diagrams 17 Radio Reciever 18 19 Accessory Wiring 19 20 Earth Ground Rod Insta...

Page 3: ...Gate Width 45 ft 13 7 m Maximum V Track Gate Width 35 ft 10 7 m 1 HP Motor Maximum Gate Speed 12 sec 30 5 cm sec Maximum Gate Weight 1700 lbs 771 1 kg Maximum Cantilever Gate Width 35 ft 10 7 m Maximu...

Page 4: ...eans of entrapment protection Both primary and secondary entrapment protection methods must be designed arranged or configured to protect against entrapments in both the open and close directions of g...

Page 5: ...t be located at least six feet 6 away from any moving part of the gate and where the user is prevented from reaching over under around or through the gate to operate the controls Outdoor or easily acc...

Page 6: ...es for Close Cycle 4 1 2 m Typical 4 1 2 m Typical Open Edge Photo Eyes for Open Cycle Run Twisted Wire from Loop to Operator STREET COMPLEX OR PARKING LOT Gate 1 Interrupt Safety Loop Photo eye for o...

Page 7: ...both inside and outside of a vehicular horizontal slide gate Non contact sensors such as photo eyes must protect during both open and close gate cycles Injuries occur when people put their hands and a...

Page 8: ...f the power disconnect should be visible and clearly labeled ALL power and control wiring MUST be run in separate conduit BEFORE installing power wiring or control stations be sure to follow all speci...

Page 9: ...e 2 2 Locate electrical conduit as required prior to pouring concrete 3 Pour concrete pad 4 Secure operator Figure 3 to the concrete pad using four 1 2 concrete anchors not provided Figure 1 Figure 2...

Page 10: ...o pouring concrete 3 Secure operator to posts using four 3 U bolts and hardware provided Figure 3 Figure 2 14 35 6 cm Min Ground Level Depth As Required By Local Codes or Below Frost Line 3 7 6 cm Out...

Page 11: ...ain slack for every 10 3 1 m of chain length Do not overtighten chain NOTE ABOUT SOME TYPES OF CANTILEVER GATES With some cantilever gates over 20 6 1 m long you may need to add a brace along the leng...

Page 12: ...ns inside the disconnect switch electrical box Refer to electrical wiring diagrams on pages 27 30 MANUAL DISCONNECT 115VOLT 1 PH USE COPPER CONDUCTO R ONLY 115VOLT 1 PH USE COPPER CONDUCTOR ONLY 115V...

Page 13: ...y to adjust the sensor for correct alignment To do so please perform the following steps 1 The sensor must be centered over the magnet wheel Adjust with horizontal screws 2 The sensor must be level 3...

Page 14: ...the gate is closing will have no effect Terminals 10 5 Obstruction While Closing Edge Photo Eye Input Edge Input See Programming Section on page 15 This input will reverse a closing gate to the open l...

Page 15: ...he gate to the open limit when activated during the close cycle The entrapment is not cleared at the limit and the timer to close will be disabled The timer to close may be enabled by activating the i...

Page 16: ...N SAVE TTC ON S1 RT LT SW SL RT LT SW SL 1 2 3 4 ON SAVE TTC ON S1 1 2 3 4 ON SAVE TTC ON S1 RT LT SW SL RT LT SW SL Factory Default TIMER TO CLOSE ENABLED SWING GATE SLIDE GATE TIMER TO CLOSE DISABLE...

Page 17: ...guidelines presented throughout the manual Installation device instructions Always follow the instructions provided by the manufacturer when installing and adjusting any control device If these instru...

Page 18: ...To prevent possible SERIOUS INJURY or DEATH from a moving gate or garage door ALWAYS keep remote controls out of reach of children NEVER permit children to operate or play with remote controls Activat...

Page 19: ...eration is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesi...

Page 20: ...any additional surge protection MASTER SECOND SYSTEMS Dual Gate Communications The control board is capable of running the operator in a master or second mode depending on S4 switch setting Before in...

Page 21: ...ground rod must be located within 3 feet from the gate operator Use the proper type earth ground rod for your local area The ground wire must be a single whole piece of wire Never splice two wires for...

Page 22: ...pair of slide swing gate operator The design of this gate system balances the demands of speed during high traffic periods with security during low traffic periods Barrier gates typically have the fa...

Page 23: ...rea Clean the operator as needed 6 It is suggested that while at the site voltage readings be taken at the operator Using a Digital Voltmeter verify that the incoming voltage to the operator it is wit...

Page 24: ...uction the clutch will slip 1 Loosen set screws of torque adjustment nut on the gear reducer output shaft 2 Back off torque nut until there is very little tension on the Belleville washers 3 Tighten t...

Page 25: ...ult Control Input 6 Loss of communications Removal of between master and problem second during run mode On No Motor not learned Completion Flash of Motor Learn Routine Hard inputs include open overrid...

Page 26: ...he operator This voltage should be within 5 of 24Vac If the high voltage power is good and the low voltage power is bad check to make sure the circuit fuse is not tripped and that the correct primary...

Page 27: ...The brake should disengage when the contactor activates and engage when the contactor releases Both LEDs will indicate the activation of entrapment protection devices on terminals TB1 9 and TB1 10 on...

Page 28: ...R AT O R S H E AT E R W I R I N G D I A G R A M F O R 2 0 8 2 3 0 4 6 0 A N D 5 7 5 V O P E R AT O R S HEATER REPLACEMENT PARTS PART NUMBER DESCRIPTION QTY 21 15453 1 Transformer 100VA with 3 2A fuse...

Page 29: ...B A A1 A2 A1 A2 RPM SENSOR GL CONTROL BOARD 24VAC IN 24VAC COMMON SOFT OPEN NC B LIMIT CONTACTOR B A LIMIT CONTACTOR A RPM IN RPM SUPPLY RPM GND RADIO COMMAND SHADOW 24VDC CLOSE STOP SOFT OPEN HARD OP...

Page 30: ...B NC C YEL BLK Y BK GY TB2 BL Y PU GY BL Y PU 1 3 8 5 4 2 OL BK BK BK BK BL BK BL BK 115V BRAKE SOLENOID 115V CONNECTION 230V BRAKE SOLENOID 208 230V CONNECTION BL BK BL BK 4 5 2 3 8 1 LOOP WIRING TB...

Page 31: ...RD WH PU P W Y BK GN Y BK Y BK WH BRN BRN OR GN GY OR BK WH RD BK BK BL YE GY BRN GY BRN OR Y BK GN Y BK YE YE BL BL BRN PU OR BL BL BK BK YE YE YE RD RD L3 BK BK FACTORY INSTALLED RADIO 40 32351G 3...

Page 32: ...32 T H R E E P H A S E S C H E M AT I C...

Page 33: ...0 Alarm kit Complete with Alarm spacer and faston K9 K75 18493 Chain guide kit K10 653509 Optional diagonal brace kit NOT SHOWN 71 6532449 Heater kits Optional 115 575V Operators 71 6532448 Heater kit...

Page 34: ...5 34842 10 2 1 K1 71 B120 71 B240 71 B575 K2 K75 10177 6 K4 K75 34824 4 3 4 3 K3 K75 34828 K6 K75 34790 K7 K75 34791 K8 K29 32410 8 K9 K75 18493 K10 653509 I L L U S T R AT E D P A R T S M O D E L 5 8...

Page 35: ...larm kit Complete with Alarm spacer and faston K7 K75 18493 Chain guide kit NOT SHOWN 71 6532449 Heater kits Optional 115 575V Operators 71 6532448 Heater kits Optional 208 230 460V Operators K50 1842...

Page 36: ...AT E D P A R T S M O D E L 5 9 5 3 6 12 13 4 5 6 1 2 7 8 9 11 K3 K75 12858 K1 71 B120 71 B240 71 B575 K2 K75 18618 K4 K75 18620 K6 K29 32410 K5 K72 18615 19 18 18 16 17 15 10 14 K7 K75 18493 312HM Rec...

Page 37: ...erload 10 AMP SL585 50 11 SL595 50 11 SL585 150 21 SL595 150 21 25 2015 Overload 15 AMP SL585 100 11 SL595 100 11 25 2025 Overload 25 AMP SL585 150 11 SL595 150 11 Non stocked item Please allow additi...

Page 38: ...9 m Maximum Range 24V ac dc SENSING EDGES MODEL DESCRIPTION VOLTAGE G65MG0204 Miller MG020 2 wire electric edge for gates Sensitized on three sides 24V ac dc Requires mounting channel 4 1 2 m long G65...

Page 39: ...39 N O T E S...

Page 40: ...ation may not apply to you THIS LIMITED WARRANTY DOES NOT COVER NON DEFECT DAMAGE DAMAGE CAUSED BY IMPROPER INSTALLATION OPERATION OR CARE INCLUDING BUT NOT LIMITED TO ABUSE MISUSE FAILURE TO PROVIDE...

Reviews: