Controls and Accessory Installation

21

Doc 01-G0665

Rev C

Controls and Accessory Installation

See wiring diagram for more information.  See Wiring Specifications on p. 9 for wiring
distances and wire gauge information.

All inputs are normally open and momentary, except the stop (NC), and emergency close and
emergency open (constant pressure).  The following instructions are based upon UL 325, dated March
of 1999 and include recommendations for significant increase in safety.

We strongly recommend that you follow the UL guidelines presented throughout the manual.
Installation device instructions – always follow the instructions provided by the manufacturer when
installing and adjusting any control device.  If these instructions are contrary to the advice given here,
call for assistance.

WARNING

All controls that are to be used to operate the gate system must be installed where the user
cannot touch the gate while operating the controls.  Also, always install the controls where the
user has full view of gate operation.

RECEIVER

CONTROL PANEL

TERMINAL STRIP

RADIO

1

2

3

ON SIDE  OF

R1

R3

R2

GATE LOCK

POWER

E- OPEN

E- CLOSE

INTERRUPT LOOP

This input is for vehicles only and does not

provide UL secondary safety for persons.  This 

functions as an wireless open unless on the 

close limit where it is defeated - thus preventing

vehicles from entering freely.

 

These are constant pressure inputs that

bypass the processor and may be used only

in an emergency if the processor fails.

Note left/right switch does not effect direction.

 

STOP BUTTON

- REQUIRED -

This is a normally closed input and the operator 

will not run unless this is installed!

USE POWER TO MATCH GATE LOCK

 

REQUIREMENTS, NOT TO EXCEED

115V 10A.

For warning devices,

call the factory

24

V

A

C

SUPERVISED

OPEN BUTTON

Caution - Only wired devices in sight of the

gate may be used with this input.

 

(WIRELESS) UNSUPERVISED

 OPEN BUTTON

Any device can be used here and the radio

(R2) is wired here internally by the factory.

Note, on a second inherent obstruction, this

input will not function (disabled).

CLOSE/SINGLE BUTTON

 

5

7

5

8

5

6

5

4

EXTERNAL ENTRAPMENT OPEN

 

Will reverse (close) the gate if active.  If

entrapment 

 

is sensed during a reversal, the

gate will stop.  May defeat the timer to close.

SECONDARY SAFETY

It is recommended that secondary 

safeties always be used for both 

the open and close directions.  

Use safety edges. In 

the 

any case,

device must sense people.

Loops cannot be used.

 

EXTERNAL ENTRAPMENT CLOSE

Will reverse (open) the gate if active. If

entrapment is sensed during a reversal the

gate will stop. May defeat the timer to close.

9

OPEN

5

10

CLOSE

5

2

3

1

3

5

13

14

Use shielded twisted pair.

do not run with power wiring.

MASTER/SLAVE

11

11

12

12

01-G0665F19

Figure 19

NOTE: 

Numbers shown inside a box are on the J1 terminal strip on the circuit board.

Connections shown here are field connections.  The radio receiver may be ordered factory
installed.

Summary of Contents for LiftMaster Professional SW470

Page 1: ...Doc 01 G0665 Rev C Installation and Maintenance Instructions Medium Heavy Duty Swing Gate Operators Models SW470 SW490...

Page 2: ...__ 12 Pad Mount Installation _______________________________________________________________ 13 Control Arm Assembly _______________________________________________________________ 14 Gate Bracket Ins...

Page 3: ...__________________________________________ 27 SW490 Parts List____________________________________________________________________ 28 Warranty Policy___________________________________________________...

Page 4: ...AD BOLT 2 82 NH38 06 3 8 16 X 3 8 CONE POINT SET SCREW 4 84 RH 75 3 4 10 HEX NUT 2 85 LS 38 3 8 SPLIT LOCKWASHER 2 Table 1 Parts Supplied Model Classifications RESIDENTAL VEHICULAR GATE OPERATOR CLASS...

Page 5: ...eneral Information 5 Doc 01 G0665 Rev C Specifications Model HP Max Wt Lbs Max Gate Width SW470 50 500 12 FT SW490 33 1 3 600 12 FT SW490 50 750 16 FT SW490 75 900 19 FT SW490 100 1 1000 22 FT Table 3...

Page 6: ...ot intended to be comprehensive Because each application is unique it is the responsibility of the purchaser designer installer and end user to ensure that the total gate system is safe for its intend...

Page 7: ...3 Leave Installation and Maintenance Manual and Safety Information with end user FOR GATE OPERATORS USING NON CONTACT SENSOR S See instruction supplied with sensor for proper placement Precautions mus...

Page 8: ...to the swing gate system to assist in the protection of people who may come near the gate operating system Also injuries can occur when people put their hands and arms through openings in a grill type...

Page 9: ...allows for a 5 voltage drop C Supply voltage must be within 10 of the operator s rating under load conditions D These calculations are based on stranded copper wire E It is highly recommended that on...

Page 10: ...425 5 700 8 900 8 150 600 900 3 600 5 625 10 100 375 575 2 275 3 525 12 75 250 375 1 425 2 225 Table 5 Power Wiring Chart System Features ACTIVITY LED Steady indication when gate is at either open or...

Page 11: ...uired by the class of operator both an open and close protection device must be used SPECIAL NOTE ABOUT OBSTRUCTION SENSING FROM EITHER INTERNAL OR EXTERNAL SYSTEMS The operator will stop if it senses...

Page 12: ...ions are for right hand operator installation Left hand is opposite 01 G 0665F1 Figure 4 Post Mount for SW470 Operator Only 1 Locate mounting post and electrical conduit locations The operator cabinet...

Page 13: ...ncrete 3 Pour concrete insuring that pad is level and above ground line 4 Locate 4 X 6 minimum length L Bolts not supplied These should protrude 1 inch above pad 5 Allow concrete to set at least two d...

Page 14: ...ol arm extension to control arm on operator with 2 3 8 16 x 1 long hex head bolts and lockwashers Use holes that are appropriate for degree of gate opening required 01 G 0665F3 Figure 8 3 Assemble the...

Page 15: ...control arm extension to arm hub with 20 black plastic knobs provided as shown in Figure 10 Place hub onto shaft with key and secure using set screw Be sure rubber seal is on end of hub to keep water...

Page 16: ...tension 01 G 0665F6 Figure 12 2 Adjust the eccentric stop as shown so that the wide area of the eccentric is against the arm Be sure that the control arm and actuator are in a straight line Install th...

Page 17: ...on 2 Loosed set screw on open limit cam 3 Rotate the open limit cam in the dame direction as the shaft turns to open the gate Stop at the point at which the cam just clicks the limit switch 4 Tighten...

Page 18: ...th this unit All single phase operators will have L1 neutral L2 hot and ground All three phase operators will have L1 L2 L3 and ground It is very important that operator is properly grounded IMPORTANT...

Page 19: ...ocked out at the factory to activate the timer to close move timer disable jumper from bottom two pins show illustration to top two pins Then set time per the chart on page 20 To lock the timer to clo...

Page 20: ...N OFF 141 SEC 144 SEC ON ON OFF OFF 155 SEC 158 SEC OFF ON OFF OFF 167 SEC 170 SEC ON OFF OFF OFF 180 SEC 183 SEC OFF OFF OFF OFF 194 SEC 197 SEC Table 8 Switch 2 Timer to Close Timer to close is lock...

Page 21: ...y These are constant pressure inputs that bypass the processor and may be used only in an emergency if the processor fails Note left right switch does not effect direction STOP BUTTON REQUIRED This is...

Page 22: ...not already done so temporarily connect a three button station to the operator Test for proper open stop and closing of the gate Test the internal obstruction sensor system Test for proper operation...

Page 23: ...require more frequent maintenance checks C Inspection and service should always be performed anytime a malfunction is observed or suspected D Limit switches may have to be reset after any major drive...

Page 24: ...otor does not run when OPEN or CLOSE button is pressed Building fuse blown or circuit breaker tripped Replace fuses or reset breaker and check for cause Overload protector tripped Reset and check for...

Page 25: ...SW470 Parts List and Drawing 25 Doc 01 G0665 Rev C SW470 Parts List and Drawing SW470 Exploded View Figure 20...

Page 26: ...1 S3 BOARD 10 2101 1 T 1 WRAPPER HOUSING 75 G0089 3 ACTUATOR COLLAR ASSEMBLY 10 2101 2 T 1 BASE PLATE 76 G0597 1 ALARM ASSEMBLY 10 2103 T 1 REDUCER BRACKET 76 G0541 1 HALL EFFECT ASSEMBLY 10 2104 T 1...

Page 27: ...SW490 Parts List and Drawing 27 Doc 01 G0665 Rev C SW490 Parts List and Drawing SW490 Exploded View Figure 21...

Page 28: ...LAR 10 G0539 1 SENSOR SUPPORT BRACKET 76 G0541 1 HALL EFFECT ASSEMBLY 10 G0614 1 ELECTRICAL PANEL 76 G0564 1 ALARM ASSEMBLY 10 G0671 1 CONTROL BOARD BRACKET 80 1003 1 TINNERMAN NUT 11 2002 1 MAIN SHAF...

Page 29: ...C 30 60hz SW490 33 53 SW49000 50 53 20 3100M 5T MOTOR 3 4 HP 575VAC 30 60hz SW490 33 53 SW490 50 53 21 XXXX 21 3260 TRANSFORMER 24V 50VA ALL 115 208 230 460VAC 1PH 3PH 21 10298 TRANSFORMER 575V 3PH AL...

Page 30: ...PLIED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE AND OF ANY OTHER OBLIGATIONS OR LIABILITY ON SELLER S PART THIS LIMITED WARRANTY DOES NOT COVER...

Page 31: ...aster The software and firmware included in the LiftMaster product as they relate to this documentation are also protected by copyright and contain information proprietary to LiftMaster FOR TECHNICAL...

Reviews: